RF Keyfob Battery Failure
No description defined
3 -Output Failure
–
Onboard Output Failure
On-board output 1 to 2 fault
The on-board output 1 to 2 is detected as short circuit, open circuit or over current status, the
on-board output 1 to 2 fault will occur. After the output is recovered and Reset command
executed, the fault will be recovered.
Fault conditions:
When the output is at short circuit, open circuit or over current status, the fault occurs.
Recovery conditions:
After the output is recovered, the fault will be recovered.
Fault monitoring:
1.
The on-board output 1 to 2 fault is detected, the report will be sent to the relevant path.
2.
The fault indicator on the keypad flashes slowly
3.
When the on-board output 1 to 2 fault recovers, the report will be sent to the specified
path. If currently there are not other faults and Reset command executed, the fault
indicator of the keypad will go off.
4 -Keypad Failure
Condition:
Keypad fail is reported at any time when communication fails between the panel and address
1 keypad.
Restore:
Communication between panel and keypads comes back to normal and fault is reset.
Supervise:
1.
Report the keypad fault to the configured destination programmed on address 124.
2.
Flash FAULT indicator on the other keypad in normal operation (refer to the detailed
description in chapter keypad indicators).
3.
Keypad missing communication with the panel performance as below:
–
Stop detection on the keypad button
–
Flash FAULT indicator
–
The disconnected keypad do not sound FAULT beeping per minute
4.
When the keypad fault is reset, send the restore report to the configured destinations.
The FAULT indicator is turned off when there is no other system fault.
5- System Failure
–
Date and Time not set
Condition:
Date and time is not set after the system is powered on.
Restore:
Date and time is programmed and the fault is reset. Refer to Section 3.1.1 Setting date and
time for more information.
Supervise:
1.
Report the date and time fault to the configured destination programmed on location
124.
2.
Slow flash FAULT indicator (refer the detailed description in chapter keypad indicators)
74
en | Settings
AMAX panel 4000 / AMAX panel 4000
EN
2013.07 | 03 | F.01U.267.112
Installation Guide
Bosch Sicherheitsysteme GmbH