Locking within the period of alarm output time. Repeating the process of alarm locking in the
period of alarm output time, without limit to times.
Zone Tamper
The system supports the tamper detection of the zone. This function ensures that the zone is
in normal operating status. The process is as follows:
1.
If 24-hour zone tamper is enabled, the wiring method for two-terminal resistor is
required.
2.
If the zone detects that the 24-hour tamper is triggered, the zone tamper alarm will be
processed the same as 24-hour zone.
3.
If the zone detests zone alarm, the zone will process according to specified zone type.
If the zone is programmed to disable 24-hour zone tamper, the wiring method for single-
terminal resistor is required. If the zone detests alarm, the zone will process according to
specified zone type.
Zone Status Reporting
The alarm control panel reports zone status according to the specified path, including alarm,
zone fault, zone bypass and zone tamper alarm.
Zone Chime Mode
The system will support the chime mode.
The process is as follows:
–
If the chime mode is used and a zone is triggered the keypad buzzer will sound for 1
second (only in disarmed status)
Zone Pulse count
The system will support the pulse count mode.
The process is as follows:
–
pulse count duration time must be configured (Refer to chapter 9.1 Communication and
Report Settings)
–
pulse count for a zone can be set to a value between 1 and 9 (0 = disabled)
The process is as follows:
–
an alarm is only created, if the zone is triggered as many times as the value “pulse count”
within the time “count duration”.
Domestic No.
The system will support the domestic call mode.
The process is as follows:
–
If the domestic call mode is configured for a zone and an alarm from this zone is created
the alarm will be reported to the destination(s) configured and needs acknowledgement.
Cross Zone
The cross zone option works as follows:
Prerequisites:
–
At least two zones in the same area have option Cross Zone enabled
–
System option Cross Zone Timer is set to a value higher than 0
When one of these zones is triggered for more than 20 seconds, an alarm is created.
When one of these zones (the first zone) is triggered for a shorter time than 20 seconds, the
cross zone timer starts, no alarm is created at this time.