Danger!
Special care is required in connecting the positive (red) wire and the “BATT +” port of the
alarm control panel. If short-circuiting with the “BATT +” port of the alarm control panel or the
enclosure, electric arc will occur. To remove the battery from the control panel, the positive
wire of the battery should be disconnected first.
1.
Place the battery on the bottom of the module.
2.
Position the red and black wires supplied with the battery.
3.
Connect one end of the black wire to the "BATT -" port of the alarm control panel, the
other end to the negative (-) pole of the battery.
4.
Connect one end of the red wire to the "BATT +" port of the alarm control panel, the
other end to the positive (+) pole of the battery.
After the backup battery and the main power are connected, once the installation is
completed, the alarm control panel will began to charge the battery.
Red Lead
Black Lead ( - )
Backup Battery
Figure 6.2: Connection of Battery
System Power Up
After the system is powered up, set date and time. Otherwise, the system prompts as fault.
After the system is powered up or reset, it resets to previous arming / disarming status.
To reduce false alarms caused by system power-up (or by power supply restoration after both
mains supply and AUX power supply fail), the system is designed to not perform zone test
within one minute after power-up.
6.3
30
en | Installation
AMAX panel 4000 / AMAX panel 4000
EN
2013.07 | 03 | F.01U.267.112
Installation Guide
Bosch Sicherheitsysteme GmbH