Zones
Zone Inputs
On-board Inputs:
There are 8 onboard hard-wired inputs for AMAX panel 4000 / AMAX panel 4000 EN. An
additional input is provided for enclosure tamper but does not subtract from the 8 onboard
totals.
On-board Zone Response Time:
Each on-board zone response time is:
Zone Status trigger time >= 400ms, must response
Zone Status trigger time < 300ms, no response
On board Zone EOL
1.
Single EOL: If zone tamper function is not selected, each zone uses a single 2.2k ohm
EOL. The panel can detect the zone as short, normal or open.
Loop Resistance (ohm)
Zone Status
Min
Type
Max
0
1430
triggered
1650
2200
2750
normal
2970
∞
triggered
The detectors (sensors) will be connected between zone and COM terminal through EOL
series connection (open triggered) or EOL parallel connection (short triggered).
COM
Zone
The detectors (sensors) will be connected between zone and COM terminal through EOL
series connection (open triggered) or EOL parallel connection (short triggered).
COM
Zone
The panel sets the short/open as activate when connecting with single EOL.
The valid zone number is 1-8 for AMAX.
1.
Dual EOL: If the tamper supervision is set, we only can use the NC contact point. The EOL
status is:
7.2
7.2.1
46
en | Settings
AMAX panel 4000 / AMAX panel 4000
EN
2013.07 | 03 | F.01U.267.112
Installation Guide
Bosch Sicherheitsysteme GmbH