INSTALLATION MANUAL
ACCESS MENUS Fig. 1
autoset
Exit Menù
Confirm/Switch on display
Scroll up
Scroll down
See PARAMETERS MENU
See LOGIC MENU
language
stat
- +
- +
OK
vers
bft . . .
+
/
-
OK
0000
+
/
-
+
/
-
n. cycles
OK
OK
01.33
password
0---
10--
150-
1520
prg
00
- +
err
02.01
........
30.15
+
/
-
n. remotes
List of last 30 errors
Control unit
software version
No total
manoeuvres(in hundreds)
No radio control
devices memorised
ALT
follow the user guide
x2
0---
10--
150-
1520
ok
*** Password entry.
Request with Protection Level
logic set to 1, 2, 3, 4
***
** Only active on LEO B CBB 3 230 L02
**
See RADIO MENU
hidden butt
release
desired button
Add. 2ch
hidden butt
release
desired button
hidden butt
release
desired button
Add. 4ch
hidden butt
release
desired button
Add. 1ch
Add. 3ch
If cancelled
If not present
If clone, it is disabled
(
0001
)
ok
KO
dis
erase 1
erase 64
Diagnostics code
DESCRIPTION
NOTES
STRE
START E external start input activated
STRI
START I internal start input activated
OPEN
OPEN input activated
CLS
CLOSE input activated
PED
PED pedestrian input activated
TIME
TIMER input activated
STOP
STOP input activated
PHOT
Activation of PHOT photocell input or, if configured as verified photocell,
Activation of the associated FAULT input
PHOP
Activation of PHOT OP opening photocell input or, if configured as
active verified photocell only when opening, Activation of the asso-
ciated FAULT input
PHCL
Activation of PHOT CL closing photocell input or, if configured as active
verified photocell only when closing, Activation of the associated
FAULT input
BAR
Activation of BAR safety edge input or, if configured as verified safety
edge, Activation of the associated FAULT input
BAR 2
Activation of BAR safety edge input on slave motor (opposing door
connection) or, if configured as verified safety edge, Activation of the
associated FAULT input
baro
Activation of BAR safety edge input with ACTIVE reversal ONLY WHILE OPENING,
or, if configured as verified safety edge active only while opening, Activation
of the associated FAULT input
barc
Activation of BAR safety edge input with ACTIVE reversal ONLY WHILE CLOSING,
or, if configured as verified safety edge active only while closing, Activation
of the associated FAULT input
SWC
SWC motor closing limit switch input activated
SWO
SWO motor opening limit switch input activated
SET
The board is standing by to perform a complete opening-
closing cycle uninterrupted by intermediate stops in or-
der to acquire the torque required for movement.
WARNING! Obstacle detection not active
ER01
Photocell test failed
Check photocell connection and/or logic settings
ER02
Safety edge test failed
Check safety edge connection and/or logic settings
ER03
Opening photocell test failed
Check photocell connection and/or parameter/
logic setting
ER04
Closing photocell test failed
Check photocell connection and/or parameter/
logic setting
ER05
Safety edge test on slave motor failed (opposite leaves connection) Check safety edge connection and/or parameter/
logic settings
er06
8k2 safety edge test failed
Check safety edge connection and/or parameter/
logic settings
ER07
Opening safety edge test failed
Check safety edge connection and/or parameter/
logic settings
ER08
Closing safety edge test failed
Check safety edge connection and/or parameter/
logic settings
ER1x
*
Board hardware test error
-Check connections to motor
-Hardware problems with board (contact technical assistance)
ER3x
*
Reverse due to obstacle - Amperostop
Check for obstacles in path
ER5x
*
Communication error with remote devices
Check connection with serial-connected accessory devices
and/or expansion boards
ER70, ER71
ER74, ER75
Internal system supervision control error.
Try switching the board off and back on again. If the
problem persists, contact the technical assistance
department.
ER72
Consistency error of the control unit’s parameters (Logics and Parameters)
Pressing OK the detected settings are confirmed. The
board will keep on working with the detected settings.
The board settings must be checked (Parameters and Logics)
ER73
D-track parameter error
Pressing OK, the board will keep on working with D-track
as a default.
An autoset is required
ERf0
Limit switch error
check limit switch connections
erf1
Limit switch error always active after operation start
Check limit switch and motor connections
ERf3
Error in setting the SAFE inputs
Check the setting of the SAFE inputs is correct
*
X
= 0, 1, .., 9, A, B, C, D, E, F
35.40
Obstacle threshold
Instantaneous force motor
**
LEO B CBB 3 230 L02 - LEO B CBB 3 120 F02
-
33
D812916 00100_01
ENGLISH