Installation & Commissioning
Checklist
The following checklist is a summary of what is required. Refer to the relevant pages for
further details.
●
Review the section headed ‘Safety Information’ on page
●
Ensure that ‘
Power Supply Requirement
17 have been understood.
●
Confirm that Cat5 cable has been specified.
●
Install the system according to instructions in this section.
●
Check/set the door controller settings.
●
Check/set the phone isolator jumper and switch settings.
Wiring
Refer to the diagrams from page 20 onwards as appropriate for the equipment you have.
All wiring is carried out using a mixture of Cat5 for the signal wiring and 1mm² (or greater)
cores for the power wiring; refer to Page
Error! Bookmark not defined.
for further details.
It is strongly recommended that a consistent colour code be used throughout such as that
indicated on the connection diagram. Certain signals must be interconnected using a
twisted pair from the Cat5 cable. These are clearly marked on the connection diagram
and should be strictly observed.
Door Controller
The door controller and power supply should be wall-mounted in a convenient cupboard or
other protected environment with available mains power. Cable length to the entrance
should be less than 50m. The door controller for the second and subsequent entrances
may be situated in the same location, or to meet the 50m requirement may be situated in
another location. Power supplies may be shared between door controllers placed in the
same location, but controllers in separate locations must be separately powered.
Phone Isolator
The Phone isolator(s) and power supply(ies) should be wall-mounted in a convenient
cupboard or other protected environment with available mains power. Cable length to the
hone should be less than 150m, see ‘Cable Distances’ page
18. In many cases the phone
isolators will be in the same location as the door controller(s), but they may be distributed
as required to reduce wiring distances. Power supply provision can be varied beyond the
tables above, for details see the alternate cabling supplements.
Gate Controller
The gate switch controller BSSW is wired between the block door controllers and the
phone isolators, so would normally be wall mounted next to a door controller.
For further details see the “bell
issimo
and Bellcall Manual Gate and Block (PD-
120)”.