bellagio Digital Entry System 

PD

281 Issue 1 

Installation and Operating Manual 

Page 35 of 52 

 

 

 

Unused outputs must have a wire link placed between O and T on 
their terminal block.  

 

 

 

Example: 

If the 1

st

 floor has flats 1, 2, 3 and the 2

nd

 floor has flats 4, 5, 6 and one Isolator is used for 

each floor. The 4

th

 Phone output on the 1

st

 floor Isolator will need disabling; otherwise two 

outputs will try to ring flat 4. 

 

Special addressing 

On the rare  occasion when flat numbers  skip every other number, e.g.  1,3,5,7 or 2,4,6,8 
etc 

the jumper on the ‘PROG’ 6 pin header can be moved to pins 3 and 4.

 

If  flat  numbers  are  required  in  the  range  3200  to  6400  the  jumper  on  the 

‘PROG’  6  pin 

header can be moved to pins 5 and 6. This simply adds an offset of +3200 to any address 
set on SW6 and SW7. 

 

Alphanumeric Flat Numbers 

Flat numbers requiring alphabetic characters (e.g. A1-A8, B101-B108, 101C-108C) cannot 
be programmed on the Isolators and must be programmed into each individual telephone. 
Please contact Bell System for instructions in this case. 

 

 

Содержание bellagio

Страница 1: ...lagio Digital Audio Door Entry System Installation Operation Manual This manual applies to the following BFD DIG Digital Door controller Version 2 Build 3 and up BS LX Audio Phone 801 Audio Phone Version 4 onwards DBA 4I Phone Isolator DBA 8Z Zone Isolator ...

Страница 2: ...try System PD 281 Issue 1 Installation and Operating Manual Page 2 of 52 801 Audio Phone 801 Deskphone BS LX Audio Phone 801 Deskphone DBA 4I Phone Isolator DBA 8Z Zone Isolator BFD DIG controller Bellagio Entrance Panel ...

Страница 3: ...ll Isolation 13 Diagram 10 Isolator Interconnections single PSU required 14 Diagram 11 Isolator interconnections separate Power supply 15 Diagram 12 Entrance interconnections BFD DIG 16 Power Supply Requirements 17 Cable Specification 17 Cable Distances 18 Installation Commissioning 20 Checklist 20 Wiring 20 801 Audio Phone 23 BS LX Audio phone 23 Commissioning 24 Settings 24 Testing Connecting 24...

Страница 4: ...ation Diagram Nos Zone Isolation Diagram Nos 1 Entrance Up to 32 ways Overview 1 6 7 9 10 Overview 3 6 7 8 10 1 Entrance 32 64 ways Overview 2 6 7 9 11 Overview 4 6 7 8 11 Multi entrance Up to 32 ways Overview 1 5 6 7 9 10 12 Overview 3 5 6 7 8 10 12 Multi entrance 32 64 ways Overview 2 5 6 7 9 11 12 Overview 4 5 6 7 8 11 12 ...

Страница 5: ...bellagio Digital Entry System PD 281 Issue 1 Installation and Operating Manual Page 5 of 52 Overview 1 Full Isolation 1 entrance up to 32 phones ...

Страница 6: ...bellagio Digital Entry System PD 281 Issue 1 Installation and Operating Manual Page 6 of 52 Overview 2 Full isolation 1 entrance 33 to 64 phones ...

Страница 7: ...bellagio Digital Entry System PD 281 Issue 1 Installation and Operating Manual Page 7 of 52 Overview 3 Zone isolation 1 entrance up to 32 phones ...

Страница 8: ...bellagio Digital Entry System PD 281 Issue 1 Installation and Operating Manual Page 8 of 52 Overview 4 Zone isolation 1 entrance 33 to 64 phones ...

Страница 9: ...bellagio Digital Entry System PD 281 Issue 1 Installation and Operating Manual Page 9 of 52 Overview 5 System Entrance interconnections ...

Страница 10: ...ch Door Controller Display Keypad Status 1 1 Prog 6 HF Prog Vol Speech Vol Panel Speaker Save Lock Power Test Cam2 Audio Video 100 75 High 100 75 High Cam1 Cam2 4 3 2 1 0 Video Gain Label BFD DIG Version No Build No Panel Tone Volume bell System 2010 Speech Unit PM 12V SPKR Exit 12V 12V Door Lock Power 2 2 M M 1 1 S S B B A A Video Camera 1 Camera 2 Video 28V Audio Audio Data Data Commn Input Outp...

Страница 11: ...bellagio Digital Entry System PD 281 Issue 1 Installation and Operating Manual Page 11 of 52 Diagram 7 Basic System Wiring Detail ...

Страница 12: ...bellagio Digital Entry System PD 281 Issue 1 Installation and Operating Manual Page 12 of 52 Diagram 8 Phone Connections Zone Isolation ...

Страница 13: ...bellagio Digital Entry System PD 281 Issue 1 Installation and Operating Manual Page 13 of 52 Diagram 9 Phone connections Full Isolation ...

Страница 14: ...bellagio Digital Entry System PD 281 Issue 1 Installation and Operating Manual Page 14 of 52 Diagram 10 Isolator Interconnections single PSU required For example 1 32 ways ...

Страница 15: ...bellagio Digital Entry System PD 281 Issue 1 Installation and Operating Manual Page 15 of 52 Diagram 11 Isolator interconnections separate Power supply For example 32 64 ways ...

Страница 16: ...bellagio Digital Entry System PD 281 Issue 1 Installation and Operating Manual Page 16 of 52 Diagram 12 Entrance interconnections BFD DIG ...

Страница 17: ...ephone or alarm cables are not suitable Bell System will be unable to offer any warranty or support for systems installed using incorrect cables Cat5 Cable Specification Cat5 is our short reference for EIA standard UTP Category 5 Unshielded Twisted Pair data cable This is a standard solid core twisted pair cable having 4 pairs 8 cores and no shield The cores are in pairs where Blue and Blue with a...

Страница 18: ...m 1 0 mm2 CAT5 PAX1 Fob reader extra to any entrance panel 3 Lock release 0 5A 4 CAT5 1A 8 1A 2 1 0mm2 Exit button 2 CAT5 Door monitor contact switch 2 System Interconnections DBA 4I DBA 8Z to Power Supply BFD DIG 8 2 CAT5 BFD DIG to BFD DIG Trades facility optional 6 1 1 Misc Power Supply to BFD DIG 2 3m 1 0mm2 TS2000 BST Time clock to BFD DIG Door controller optional 4 50m CAT5 1 There is no res...

Страница 19: ...ntrance panel only the phones which are ringing may answer the call The conversation cannot be overheard by another phone except an extension phone in the same flat i e one which had also been ringing This feature is available on systems with Full Isolation all phone models and on Zonal Isolation 801P 801PS and BS LX models only Extension sounders and flashing strobe The RT27 extension sounder can...

Страница 20: ...trictly observed Door Controller The door controller and power supply should be wall mounted in a convenient cupboard or other protected environment with available mains power Cable length to the entrance should be less than 50m The door controller for the second and subsequent entrances may be situated in the same location or to meet the 50m requirement may be situated in another location Power s...

Страница 21: ...fficers usually require a minimum of door handle or push bar to open a door on a fire exit route not a thumb turn Most fail secure locks are not continuously rated and if an electrical hold open system is used for say busy times then a continuously rated release must be used Powered bolt shoot bolt or other more secure door locking systems may require the use of separate power supplies or a suppre...

Страница 22: ... such as brick acid The panel should be cleaned only with a damp cloth containing dilute detergent Bellagio with Fob Installing the Back Box Close up of Washers The Bellagio panel is constructed to be water tolerant and it is important to install the panel carefully to avoid compromising the seals Neoprene backed washers are provided to seal the main mounting holes A 20mm conduit entry allows the ...

Страница 23: ... Page 23 of 52 801 Audio Phone Lock Button Function Mute on off Slide switch on side Model 801S or 801PS only Lock Open Door BS LX Audio phone Lock Mute Symbol Lamp Steady Flashing Mute on off Red Ringer is muted Off Hook Lock door monitor Green Door is open Press to release lock ...

Страница 24: ...h quality pluggable screw terminal blocks This enables all the connections to the system to be fully completed whilst easily isolating individual pieces of equipment during testing and commissioning Any problems can be resolved by rechecking wiring and connections assisted by the various suggestions and tests in the section Troubleshooting Connect up one entrance first leaving any connection to Is...

Страница 25: ... pins 5 6 Now pressing the test button will enter panel programming for 30S when the panel security code can be read or set When the programming is finished replace the jumper back to its original location Panel Programming First type the Panel Security Code initially 3434 followed by the bell button The display will show the first programmable parameter and the current value Numeric Entry Bell Bu...

Страница 26: ...solator output 13 Reception Yes Enables Reception function button ACCESS CODE Primary Access Code Main code to open the door Applies whenever the display indicates Enter Code The Trades Function needs to be set to Code or Trade as per the table below The code must be 4 digits and no letters leading 0 is OK e g 0246 TRADES CODE Secondary Access Code or Tradesmen s Code Secondary tradesmen s code to...

Страница 27: ...is closed Standard normally closed switch RECPTION No Reception Phone Address The reception button is used to call a reception desk or similar The number is that of the called phone The default is 9898 which is unlikely to be used by a flat SECURITY CODE Panel Security Key The security key is required to gain access to panel programming The code is entered then pressing the bell button the default...

Страница 28: ...nce repeat 13 30s 1 in 15 1 ring 15S silence repeat 14 30s 1 in 5 1 ring every 5 seconds 15 30s 1 in 3 1 ring every 3 seconds Default setting TALK TIME Talking Time Videophone Active Enter from 0 to 15 as per the table Setting Talk Time Setting Talk Time Setting Talk Time Setting Talk Time 0 15s 4 60s 8 150s 12 60s 1 20s 5 75s 9 180s 13 60s 2 30s 6 90s 10 60s 14 60s 3 45s 7 120s 11 60s 15 60s Defa...

Страница 29: ...s the number format for addressing a phone and removes the 3 Second overhang of speech when operating the lock from a phone BS801 audio phones from Build 6 or BC801 or BC801P audio phones from Build 6 and all BSA phones already have number format transparency built in and do not need this switch Default is No set to Yes only when in a mixed BCP1 with older phones Must be set to No when addressing ...

Страница 30: ...doubles the volume level and 8 presses of Vol halves it Pressing Save stores the new value Increasing the volume too far will make speech less stable and there will be a tendency for feedback intermittent screeching and howling If this happens press Vol four times and Save and test again The new level is tested by ringing one or more videophones and talking to them Finally return the jumper to its...

Страница 31: ... the panel display The Switch settings are in the table however some settings may need to made in conjunction with the Door Controller Settings E G Reception Shown Bit Function Bit Off Default Bit On 1 Spare 2 Spare 3 Spare 4 Spare 5 Spare 6 Spare 7 Concierge Display shows Reception Display Shows Concierge 8 Reception Reception Concierge Button Shown Reception Concierge Not Shown Switch QWERTYUI O...

Страница 32: ...ithin one flat will not stop phones within other flats functioning There is a maximum of 2 phones in each flat Adding a 2nd phone extension phone reduces the maximum number of flats that can be powered from the same Power supply Isolator PCB s are normally supplied in an individual ABS plastic enclosure but can be supplied in multiples in a lockable IP55 Steel cabinet with or without power supplie...

Страница 33: ...able below SW6 Value Phone address SW7 1 8 OFF SW6 Value Phone address SW7 1 8 OFF Phone 1 Phone 2 Phone 3 Phone 4 Phone 1 Phone 2 Phone 3 Phone 4 0 address not set factory default 8 29 30 31 32 1 1 2 3 4 9 33 34 35 36 2 5 6 7 8 A 37 38 39 40 3 9 10 11 12 B 41 42 43 44 4 13 14 15 16 C 45 46 47 48 5 17 18 19 20 D 49 50 51 52 6 21 22 23 24 E 53 54 55 56 7 25 26 27 28 F 57 58 59 60 Basic Addressing I...

Страница 34: ...add the Total offset value of SW7 switches to the addresses selected by SW6 See the table on page 33 Example First Floor 101 108 Second Floor 202 209 Isolator DBA 4I Address Range SW6 Position SW7 setting Comment 1 101 104 1 1 4 4 ON 100 Choose 1 4 then add offset of 100 2 105 108 2 5 8 4 ON 100 Choose 5 8 then add offset of 100 3 202 205 1 1 4 1 5 ON 201 Choose 1 4 then add offset of 201 4 206 20...

Страница 35: ...cial addressing On the rare occasion when flat numbers skip every other number e g 1 3 5 7 or 2 4 6 8 etc the jumper on the PROG 6 pin header can be moved to pins 3 and 4 If flat numbers are required in the range 3200 to 6400 the jumper on the PROG 6 pin header can be moved to pins 5 and 6 This simply adds an offset of 3200 to any address set on SW6 and SW7 Alphanumeric Flat Numbers Flat numbers r...

Страница 36: ... the lock button is pressed while the speech light is on the status LED will come on for 3 seconds if using the BS LX phone the green LED on the phone will also come on for 3 seconds 6 Press the test button at any time to cancel 7 Restore SW7 to the required address setting Diagnostic LEDs LED State Action on LED Status Power up Flashes 3 times Data is present on Data A B Brief flash Phone lock bu...

Страница 37: ...ne It offers a good compromise between equipment cost and ease of maintenance If greater isolation is required please refer to the DBA 4I Phone Isolator There is a maximum of 2 phones in each flat Adding a 2nd phone extension phone reduces the maximum number of flats that can be powered from the same Power supply Isolator PCB s are normally supplied in an individual ABS plastic enclosure but can b...

Страница 38: ...7 1 8 OFF Phone 1 Phone 2 Phone 3 Phone 4 Phone 5 Phone 6 Phone 7 Phone 8 0 address not set factory default 1 1 2 3 4 5 6 7 8 2 5 6 7 8 9 10 11 12 3 9 10 11 12 13 14 15 16 4 13 14 15 16 17 18 19 20 5 17 18 19 20 21 22 23 24 6 21 22 23 24 25 26 27 28 7 25 26 27 28 29 30 31 32 8 29 30 31 32 33 34 35 36 9 33 34 35 36 37 38 39 40 A 37 38 39 40 41 42 43 44 B 41 42 43 44 45 46 47 48 C 45 46 47 48 49 50 ...

Страница 39: ...the Total offset value of SW7 switches to the addresses selected by SW6 See the table on page 38 Example First Floor 101 116 Second Floor 202 217 Isolator DBA 8Z Address Range SW6 Position SW7 setting Comment 1 101 108 1 1 8 4 ON 100 Choose 1 8 then add offset of 100 2 109 116 3 9 16 4 ON 100 Choose 9 16 then add offset of 100 3 202 209 1 1 8 1 5 ON 201 Choose 1 8 then add offset of 201 4 210 217 ...

Страница 40: ...i Seven Phones Used disabled 123456ui Six Phones Used disabled disabled 12345yui Five Phones Used disabled disabled disabled 1234tyui Four Phones Used disabled disabled disabled disabled 123rtyui Three Phones Used disabled disabled disabled disabled disabled 12ertyui Two Phones Used disabled disabled disabled disabled disabled disabled 1 On the DBA 8Z isolator set SW7 from the table above 2 Set SW...

Страница 41: ...e entrance panel Please contact Bell System for instructions in this case Phone ring test This can be used to ring a phone on one of the 8 outputs and see off hook and lock button operation It does not test the speech 1 Press the Test button twice to ensure the system is in idle 2 Set SW7 to test the appropriate phone only one phone at a time 1 ON 1st Phone 2 ON 2nd Phone 3 ON 3rd Phone 4 ON 4th P...

Страница 42: ...Speech active call in progress Ring Test active no speech On Off hook 1 or more phones are off hook On LED1 1st Phone active On LED2 2nd Phone active On LED3 3rd Phone active On LED4 4th Phone active On LED5 5th Phone active On LED6 6th Phone active On LED7 7th Phone active On LED8 8th Phone active On Fuses The 12V connection V on either terminal block is fused with a standard 20mm fuse which will...

Страница 43: ...se models have a ring volume with 2 settings high and low marked HI and LO The default is HI If the ring is too loud move the jumper at the top left of the PCB to over the 2 pins marked LO No other adjustments are required The 801S and 801PS have a slide switch on the right to enable the user to turn the ringer on or off BS LX Phones ...

Страница 44: ... and 10 hours It can typically be used to silence the ringer over night The default setting disables the ringer until the button is pressed again not cancelling automatically Refer to the table above or the label inside the phone The settings for Ring type Door Monitor and Unlock time should be left on the defaults DIP switch 1 4 should be all OFF as they are not used on the Bellagio system Phone ...

Страница 45: ...k Fault Reference These tables provide a quick indication of the possible fault Lock Release Problems Lock release does not operate or clicks but does not open Connections to Lock Release are open or shorted Voltage drop due to cable too thin Lock current is too high Power supply is resetting Lock release jammed due to over tight fitting Maglock does not hold strongly Voltage drop due to cable bei...

Страница 46: ...should be ringing BS LX only Low Voltage to phone Check the cable requirements page 18 Check voltage between V and O on the phone when ringing Power supply voltage low due to current overload Check the voltage at the power supply is 13 14V BS LX phone flashes red and green periodically instead of ringing No 12V to connection V check 12V between V and O on the phone Check the fuse on the DBA 4I 8Z ...

Страница 47: ...Z Isolator has reset Low voltage to the DBA 4I 8Z Isolator connected to that phone Check the cable requirements page 18 Check at least 10V on the 12V connection when the phone should be ringing No speech from videophone to entrance Missing or Broken Spkr or Spkr connection No speech from entrance to videophone Missing or Broken PM or PM connection Low volume speech in one or both directions Anothe...

Страница 48: ...des display and speech Model BSSW Gate Controller Block Isolator Size 185mm x 230mm x 42mm Supply Voltage 10 8V min 13 8V typical 15V max Current consumption 80mA idle 210mA max 13 8V Model 801 801S 801P 801PS Phone Size 212mm x 85mm x 55mm Supply Voltage 8V DC minimum 15V DC maximum Current consumption 0mA idle 140mA max 13 8V Model BS LX Phone Size 235mm x 105mm x 25mm Supply Voltage 8V DC minim...

Страница 49: ...ion 29mA idle 75mA max 13 8V Phone Fuse F500mA 20mm Glass PS4 Power Supply Size 236mm x 105mm x 81mm Reg Output Voltage 13 8V Nom Output Current 3A continuous 4A peak 5 minutes max Mains Internal Fuse Not user replaceable Supply Voltage 230V 50Hz nominal Temperature Range 0 ºC to 50 ºC 840 Power Supply Battery Backup requires battery Size 350mm x 330mm x 80mm Reg Output Voltage 13 8V Nom Output Cu...

Страница 50: ...bellagio Digital Entry System PD 281 Issue 1 Installation and Operating Manual Page 50 of 52 ...

Страница 51: ...d only be connected once the system has been fully tested Connection is made by 2 leads with spade terminals observe the correct polarity red to positive black to negative Care must be taken to ensure that the terminals of the battery are not shorted together by metal objects as this may constitute a Fire Hazard The Control Cabinet is IP55 rated to exclude dust and is vented to avoid the build up ...

Страница 52: ...261106 Sales and Technical Support FAX 01908 261116 E mail sales bellsystem co uk technical bellsystem co uk Website www bellsystem co uk Standards This product complies with European directive 2014 30 EU on Electromagnetic Compatibility and Low Voltage Directive 2014 35 EU Emissions Generic BSEN 61000 6 3 Immunity Generic BSEN 61000 6 1 Low Voltage Generic BSEN 62368 1 2014 ...

Отзывы: