bellagio Digital Entry System
PD
–
281 Issue 1
Installation and Operating Manual
Page 46 of 52
Telephone Ring Problems
Phone doesn’t ring
Address not set on the DBA-4I/8Z Isolator; refer to pg.
I or O terminal not connected on the phone.
DBA-4I only
–
Phone is off-hook.
BS-LX phone:
Phone is muted. Check red light is off.
V, I or O terminal not connected:
Check for 12V between V (+) and O (-).
Check for 12V between I (+) and O (-)
(when the phone should be ringing).
Data A or B cores to DBA-4I/8Z isolator open or short
circuit or shorted to 0V or 12V at any point.
(This would affect all phones on the isolator).
Phone rings briefly then
stops
Low voltage to the DBA-4I/8Z Isolator; Check the cable
requirements page 18. Check there is at least 10V on
the 12V+/- connection when the phone should be
ringing.
BS-LX only
–
Low Voltage to phone; Check the cable
requirements page 18
; Check voltage between ‘V’ and
‘O’ on the phone when ringing.
Power supply voltage low, due to current overload.
Check the voltage at the power supply is 13-14V.
BS-LX phone flashes red
and green periodically
instead of ringing
No 12V to connection ‘V’, check 12V between V and O
on the phone. Check the fuse on the DBA-4I/8Z isolator
hasn’t blown.
Panel Display Problems
No display
No power at display, check for a minimum of 10V.
To test display, cycle the power on BFD-DIG and check
for both version numbers displayed. “BDV1” then “V4.0”
Fault Code F1
“D” connection open circuit.
Fault Code F1
“D” connection: no data received.
“D” connection shorted to 0V
Display indicates
“Call
Fail
ed”
Apartment number entered was called but did not
respond. In a large system with BSSW controller, the
panel at the gate displays Fail when the block with that
apartment number is Busy.
Otherwise see Call Problems below.