6.4 Configuration of the LioN-P
PROFINET I/O modules in STEP 7
6 Starting operation
PROFINET name:
Name not assigned
IP address:
0.0.0.0
Subnet mask:
0.0.0.0
Device designations:
0980 ESL 109-121
0980 ESL 109-122
0980 ESL 109-331
0980 ESL 109-332
0980 ESL 308-121
0980 ESL 309-121
0980 ESL 199-121
0980 ESL 199-122
0980 ESL 199-331
0980 ESL 199-332
0980 ESL 398-121
0980 ESL 399-121
Vendor ID:
0x016a
Device ID:
0x0305
6.4 Configuration of the LioN-P PROFINET I/O
modules in STEP 7
After installing the GSDML files for the LioN-P PROFINET modules, they are
available in the hardware catalog on
PROFINET IO
>
Other field devices
>
I/O
>
Lumberg LioN-P
.
First, configure the control system in the usual way. Assign an IP address and
subnet mask for the PROFINET port of the control unit.
Then click on the article designations of the modules in the hardware catalog
and move the desired module to the PROFINET line of the control unit.
6.4.1 Assigning a unique device name
PROFINET I/O devices are addressed on PROFINET via a unique device
name. This can be freely assigned by the user, but may only be used once
on the network.
Manual LioN-P PROFINET IO-Link Master
Version 2.1 10/2017