8 Diagnostics processing
8.8 IO-Link Device Diagnostics
Channel number of diagnosis
0x01 - 0x08
Channel related diagnosis
code
0x0006
Channel related diagnosis
code message
Line break
Extended description
Missing/wrong device, broken wire or short circuit/overload at Pin 4/
Ch. A of IOL-Port, detected by IO-Link Master.
8.8 IO-Link Device Diagnostics
Diagnoses of IO-Link devices that the device sends to the IO-Link Master
are reported through a standard channel diagnosis and an extended channel
diagnosis.
Standard channel diagnosis message:
Channel number of diagnosis
0x01 - 0x08
Channel related diagnosis
code
Depends on IO-Link device diagnosis
Channel related diagnosis
code message
Depends on IO-Link device diagnosis
Extended channel diagnosis message:
Channel number of diagnosis
0x01 - 0x08
Ext. channel related diagnosis
code
0x9000
Ext. channel value
EventCode << 16 | ChannelNumber << 8 | EventQualifier
Event Code
Diagnostic code reported by the IO-Link device. Use
the IOLink device documentation to interpret the error
message.
Channel Number
Manual LioN-P PROFINET IO-Link Master
Version 2.1 10/2017
83