5.3 Port assignments
5 Assembly and wiring
IO Link
Type B
Pin
Signal
Function
1
L+
IO Link sensor power 24 V
2
2L+ (U
Aux
)
Ch. B: Auxiliary power supply (electrically
isolated with respect to the sensor/system
power supply)
3
L-
IO Link sensor supply GND_U
S
4
C/Q
Ch. A: IO-Link data communication
5
2M (GND_U
Aux
)
Ground/reference potential U
Aux
Table 7: IO ports as M8 or M12 socket IO Link Type B
Warning:
IO Port – Sensor supply:
The sensor supply may only be carried out via the specified power
connection (Power X03 --> US +24 V/GND_U
S
) of the module. An
external power supply over the IO port (Port X1-X8 --> Pin1/Pin3) is
not permitted and can lead to a destruction of the module electronics!
Warning:
IO Port connection (IO Link - Class B):
The sensor supply (Port X5-X8 --> Pin1/Pin3) and the extended
sensor supply (Port X5-X8 --> Pin2/Pin5) are galvanic isolated
from each other. If the reference potentials (GND_US - Pin3) and
(GND_UAux - Pin5) are connected, unacceptable compensation
currents can flow. In this case the connection of a sensor at (Port X5-
X8 --> Pin2) is not allowed!
The removal of the galvanic separation is not recommended.
Manual LioN-P PROFINET IO-Link Master
Version 2.1 10/2017
30