11 Technical data
11.2 PROFINET protocol
11.2 PROFINET protocol
Protocol
PROFINET IO Device V2.3
Conformance Class
C (CC-C)
Netload Class
2
Update cycle
1 ms
GSDML file
GDSML-V2.3x-LumbergAutomation-LioN-Pyyyymmdd.xml
Transmission rate
100 Mbit/s, full duplex
Transmission procedure
Autonegotiation
100BASE-TX
is supported
Vendor ID
16A
H
Device ID
0305
H
(same for all LioN-P modules)
Supported Ethernet protocols
Ping
ARP
LLDP
SNMPv1 (network diagnostics)
D
Read Community: public
D
Write Community: private
DCP
HTTP
TCP/IP
MRP Client
PROFINET feature
Fast Start-UP
Shared Device
Switch functionality
Integrated
IRT is supported
PROFINET interface
Connections
Autocrossing
2 M12 sockets, 4-pin, D-coded (see pin assignments)
2 M12 Hybrid male/female, 8-pin
is supported
Electrically isolated Ethernet
ports -> PE
2000 V DC
Table 47: PROFINET protocol
Manual LioN-P PROFINET IO-Link Master
Version 2.1 10/2017
97