Commissioning
EL3692
134
Version: 2.1
Index 80n2 SAI User Data (for Ch.1 (n=0); Ch.2 (n=1)
Index (hex) Name
Meaning
Data type
Flags
Default
80n2:0
SAI User Data
Maximum subindex
UINT8
RO
0x24 (36
dec
)
80n2:0m
(odd)
Range x 4 wire / 2 wire
offset
one offset value per measuring range for user calibra-
tion (
see fig. below
)
UINT32
RW
0x00000000
(0
dec
)
80n2:0m
(even)
Range x 2/4W gain
One gain value per measuring range for user calibra-
tion
0x10000 corresponds to 1
UINT32
RW
0x10000
(65536
dec
)
Fig. 159: Offset value per measuring range for user calibration
5.12.2
Object description and parameterization
Introduction
The CoE overview contains objects for different intended applications. The following section describes the
standard objects, followed by the objects that are specific for this terminal.
Note
Parameterization
The terminal is parameterized via the
CoE - Online tab [
}
89]
(double-click on the respec-
tive object) or via the
Process Data tab [
}
86]
(allocation of PDOs).