Commissioning
EL3692
112
Version: 2.1
Fig. 138: Screenshot of System Manager, Process data
Fig.
Screenshot of System Manager, Process data
, left, shows the EL3692 with expanded process data,
variables of channel 1 are highlighted in red. On the right the process data selection is highlighted in red.
Name of the PDO
Data direction
PDO number channel
1
PDO number channel 2
SAI Inputs
Input
0x1A00
0x1A03
SAI Range
Input
0x1A01
0x1A04
SAI Inputs Real
Input
0x1A02
0x1A05
SAI Range
Output
0x1600
0x1601
Table 1: PDO/channel numbers
Note
Measured value display
The EL3692 can output the current channel-based measured value depending on the PDO
option "
Predefined PDO assignment
" in 2 different ways. As "
fixpoint"
and "
float"
. See fol-
lowing explanation:
• as 32-bit integer measuring range-dependent value, with 24-bit content "
fixpoint
"
Explanation:
Each of the 9 measuring ranges of the EL3692 extends over 1 decade (e.g. 1 .. 10 Ω). The regular
value range of
value
extends from x0 .. x00 7F FF FF for each measuring range with "x00 7F FF FF ≈