Commissioning
EL3692
133
Version: 2.1
Objects for commissioning
Index 1011 Restore default parameters
Index (hex) Name
Meaning
Data type
Flags
Default
1011:0
Restore default param-
eters
Restore default parameters
UINT8
RO
0x01 (1
dez
)
1011:01
SubIndex 001
If this object is set to "
0x64616F6C"
in the set value di-
alog, all backup objects are reset to their delivery state.
UINT32
RW
0x00000000
(0
dez
)
Index 80n0 SAI Settings (for Ch.1 (n=0); Ch.2 (n=1)
Index (hex) Name
Meaning
Data type
Flags
Default
80n0:0
SAI Settings
Maximum subindex
UINT8
RW
0x3E (62
dez
)
80n0:01
Enable vendor calibra-
tion
Manufacturer calibration is active.
BOOLEAN
RW
0x01 (1
dec
)
80n0:02
Enable user calibration User calibration is active.
BOOLEAN
RW
0x00 (0
dec
)
80n0:05
Enable delay time
The set
delay time [
}
133]
for this channel is active.
BOOLEAN
RW
0x00 (0
dec
)
80n0:09
Disable Autorange
The Autorange function is disabled.
Is only saved if the output data are not active.
BOOLEAN
RW
0x00 (0
dec
)
80n0:0D
Mode
Measuring mode of the terminal:
0: 4-wire measurement
1: 4-wire measurement (single-shot mode)
2: 2-wire measurement
3: 2-wire measurement (single-shot mode)
Is only saved if the output data are not active.
Bit-Field[4]
RW
0x00 (0
dec
)
80n0:11
Range
Measuring range:
-1: 10 mΩ - 100 mΩ
0: 100 mΩ - 1 Ω
1: 1 - 10 Ω
2: 10 - 100 Ω
3: 100 - 1 kΩ
4: 1 k - 10 kΩ
5: 10 k - 100 kΩ
6: 100 k - 1 MΩ
7: 1 M - 10 MΩ
Is only applied if the output data are not active.
INT8
RW
0x00 (0
dec
)
80n0:1D
Presentation
0: left-aligned
1: right-aligned
2: scaled 1 bit / µΩ
3: scaled 1 bit / mΩ
4: scaled 1 bit / Ω
5: Display as REAL value
See also:
Specific data [
}
115]
Bit-Field[4]
RW
0x01 (1
dec
)
80n0:21
Filter Settings
Setting the hardware filter in ADC
0: 2.5 Hz
1: 5 Hz
2: 10 Hz
3: 15 Hz
4: 25 Hz
5: 30 Hz
6: 50 Hz
7: 60 Hz
8: 100 Hz
UINT16
RW
0x02 (2
dec
)
80n0:31
Delay time
Delay time for this channel
n*20 ms in the measuring ranges <1 MΩ, n*50 ms in
the measuring range 7 (1 MΩ - 10 MΩ)
UINT8
RW
0x00 (0
dec
)
80n0:3E
Steady state tolerance If the last four values are no more than x / 1024 of end
value apart, the "Steady state" bit is set to TRUE
UINT16
RW
0x00 (0
dec
)
Objects for the user calibration
User calibration offers the option to process the value of the terminal further after manufacturer calibration.
This can relieve the PLC.