Product overview
EL3692
13
Version: 2.1
2.3
Technical data
Technical data
EL3692
Number of inputs
2
Connection technology
2 or 4 wire
Measuring range
10 mΩ .. 10 MΩ in 9 measuring ranges
(0.01 .. 0.1 Ω, 0.1 .. 1 Ω, 1 .. 10 Ω, 10 .. 100 Ω, 100 .. 1000 Ω, 1 .. 10 kΩ,
10 .. 100 kΩ, 100 .. 1000 kΩ, 1.. 10 MΩ)
Resolution
24 bits incl. sign
Conversion time
10 ms ..400 ms; depends on measuring range; operation mode
(alternating, one channel), waiting time, filter settings
Broken wire detection
yes
Internal resistance
>100 MΩ
Filter characteristics
Hardware 5 kHz, Firmware adjustable 2.5 - 100 Hz
Measuring error
<0.5% (relative to the respective full scale value with 4-wire connection)
Supply voltage for electronics
via the E-bus
Current consumption via E-bus
typ. 220 mA
Distributed Clocks
No
Special features
automatic range selection; "auto range", pulse and continuous
measurement
Width in the process image
max. 24 bytes input, max. 4 bytes output
Electrical isolation
1500 V (E-bus/field voltage)
Configuration
via TwinCAT System Manager
Weight
approx. 60 g
permissible ambient temperature
range during operation
0 °C ... + 55 °C
permissible ambient temperature
range during storage
-25 °C ... + 85 °C
permissible relative humidity
95 %, no condensation
Dimensions (W x H x D)
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
Mounting [
}
25]
on 35 mm mounting rail conforms to EN 60715
Vibration/shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
see also
installation instructions for terminals with increased mechanical
load capacity [
}
27]
EMC immunity/emission
conforms to EN 61000-6-2 / EN 61000-6-4
Protection class
IP20
Installation position
variable
Approval
CE
cULus [
}
144]
2.4
Start
For commissioning:
• Install the EL3692 as described in chapter
Mounting and wiring [
}
25]
.
• configure the EL3692 in TwinCAT or another EtherCAT Master as described in the chapter
Commissioning [
}
37]
.