Commissioning
EL3692
105
Version: 2.1
Fig. 136: EL3692 representation in the TwinCAT System Manager
• The EL3692 provides the following outputs for each channel:
◦
SAI Inputs:
current status
◦
SAI Inputs:
current measured value 32 bit integer,
measuring range-dependent
◦
SAI Range::
current range (automatic measuring range selection)
◦
SAI Inputs Real:
current measured value 32 bit PLC fixed-point float,
measuring range-
independent, scaled representation
Please note the information relating to the
process data [
}
111]
.
5.
for 2-wire measurement:
In CoE entry x80n0:0D set the mode to 2 (n stands for the channel: 0 = channel
1, 1 = channel 2).
If necessary the EL3692 can be reset to the factory settings via a
CoE reset [
}
156]
.
Note
Measured value display
The EL3692 can output the current channel-based measured value depending on the PDO
option "
Predefined PDO assignment
" in 2 different ways. As "
fixpoint"
and "
float"
. See fol-
lowing explanation: