Commissioning
EL3692
119
Version: 2.1
Fig. 141: Calculated maximum relative measuring error relative to the current measured value in the
respective measuring range
Example from above: 50 Ω -> max. error 0.5 Ω, corresponding to 1% relative measuring error. The grey area
is only shown for illustration and is not a valid measuring range.
5.7.6
Resolution
The following table shows the resolution for each measuring range.
Measuring range
Measured variable
Resolution
-1 (0xFF/255)
10 m Ω - 0.1 Ω
11.9 nΩ/Digit
0
100 m Ω - 1 Ω
119 nΩ/Digit
1
1 Ω - 10 Ω
1.19 µΩ/Digit
2
10 Ω - 100 Ω
11.9 µΩ/Digit
3
100 Ω - 1 kΩ
119 µΩ/Digit
4
1 kΩ - 10 kΩ
1.19 mΩ/Digit
5
10 kΩ - 100 kΩ
11.9 mΩ/Digit
6
100 kΩ - 1 MΩ
119 mΩ/Digit
7
1 MΩ - 10 MΩ
1.19 Ω/Digit
5.8
Data processing
Table of contents
•
Measurement sequence [
}
120]
•
Processing sequence [
}
121]