Baxi LUNA HT 1.280 Скачать руководство пользователя страница 88

Legionella function circ pump

(1647)

  -

On

: The circulation pump will be switched on in case of active legionella functi-

on.

Caution!

 There exists a hazard of scalding at the tapping locations in case of acti-

vated legionella function.

Circulating pump release

(1660)

  -

Time programme 3

: The circulation pump is released, depending on the time

programme 3 (see prog.no. 540 to 556).

-

Drinking water release

: The circulation pump will be released, when the drin-

king water preparation has been released.

-

Time programme 4

: The circulation pump will be released, depending on the

time programme 4 of the local controller.

Circulation pump cycle opera-

tion

(1661)

  The circulation pump will be switched on for 10 minutes and off for 20 minutes

within the release time.

Zirkulationspumpe Sollwert

(1663)

  Wird ein Fühler in der Trinkwasserverteilleitung platziert, überwacht der die Re-

gelung dessen Ist-Wert während der Legionellenfunktion. Der eingestellte Soll-

wert muss am Fühler während der eingestellten Verweildauer (Prog.-Nr. 1646)

eingehalten werden. Die Einstellung des Zirkulationssollwerts wird nach oben

vom Nennsollwert begrenzt.

Optg mode changeover

(1680)

  Using external switching above the entrances H1-H5 it can be selected into which

operating mode is switched into.

-

None

: the function is switched off.

Consumercircuit

Flow temp setp cons request

(1859, 1909, 1959)

 

Setting of the flow setpoint is done with this function, which is effective during

active request of the consumer circuit.

DHW charging priority

(1874, 1924, 1974)

  Setting, if the connected consumerscircuit pump should be used with priority for

domestic hot water charging.

Excess heat draw

(1875, 1925, 1975)

  If an excess temperature discharge is activated, the excess energy can be dischar-

ged through a consumercircuit of the room heating. This can be separately set for

each consumercircuit.

With buffer

(1878, 1928, 1978)

  See prog no. 5090.

With prim contr/system

pump

(1880, 1930, 1980)

  See prog no. 5092.

Swimming pool

Setpoint solar heating

(2055)

  When using solar energy, the swimming pool is heated to the setpoint set here.

Programming

88

358 436 08.10

Содержание LUNA HT 1.280

Страница 1: ...Installation operation and maintenance manual Condensing gas boiler Power HT 1 230 1 280 1 320...

Страница 2: ...circuit water 17 4 5 Notes for installation location 18 4 6 Space requirement 19 4 7 Transportation 20 4 8 Application examples 22 4 9 Legend 31 5 Installation 32 5 1 Connect heating circuit 32 5 2 C...

Страница 3: ...g table 74 9 Maintenance 124 9 1 Inspection and need dependent service 124 9 2 Boiler view 125 9 3 Disassembling and installing burner 127 9 4 Check and replacing Ignition electrode 129 9 5 Check and...

Страница 4: ...Handbook Extended informations Usage according to purpose Technical data circuit diagram Regulations standards CE Notes for installation location Application example Standard application Commissioning...

Страница 5: ...nd life Caution If warning is not observed danger exists for environment and the device Note tip Here you can find background information and useful tips Reference to additional information in other d...

Страница 6: ...nents All electrical work in connection with the installation must only be carried out by a trained electrician Danger Danger to life if heating unit used improperly This device is not intended to be...

Страница 7: ...Industrial Gas Fired Boilers and Air Heaters IGE UP 1 Soundness Testing and Purging Procedure for Non Domestic Installa tions IGE UP 2 Gas Installation Pipe work Boosters and Compressors for Industri...

Страница 8: ...2 6 Conformity declaration Safety 8 358 436 08 10...

Страница 9: ...mensions and connections Technical Data 358 436 08 10 9 DN 65 692 1389 200 60 69 93 302 83 200 193 302 417 626 1139 flow gas DN 65 A B 163 303 389 return Model Power HT 1 230 Power HT 1 280 Power HT 1...

Страница 10: ...Technical Data 10 358 436 08 10...

Страница 11: ...60 C C 57 61 57 61 57 61 50 30 C C 30 37 30 38 30 38 w Natural gas 80 60 C g s 15 9 97 6 19 1 118 1 21 8 136 2 50 30 C g s 14 6 90 5 17 5 109 4 20 0 126 1 LPG 80 60 C g s 20 7 62 6 25 0 112 0 25 0 129...

Страница 12: ...Technical Data 12 358 436 08 10...

Страница 13: ...3 3 Wiring Diagram Fig 2 Wiring Diagram Technical Data 358 436 08 10 13...

Страница 14: ...2 15 1508 20 1224 25 1000 30 823 Tab 4 Resistance values for flow sensor KVS drinking water sensor TWF re turn sensor KRV sensor B4 Temperature C Resistance 0 32555 5 25339 10 19873 15 15699 20 12488...

Страница 15: ...d supply air connection Exhaust and supply air connection can be converted to adapt to the local conditi ons of the installation room Converting the exhaust connection In the following picture the con...

Страница 16: ...er plate 2 3 Remove the intake pipe leading upward from the intake pipe elbow 6 4 Turn intake pipe elbow 6 into the side position 5 Mount lower rear wall 5 6 Close top supply air opening acc to Fig 3...

Страница 17: ...t be treated This depends on the total water hardness system volume and the size of the boiler If in a special case a need exists to use additives in a mixture e g hardness stabil ser frost protecion...

Страница 18: ...d exist in the front to carry out in spection and maintenance work Caution Danger of damaging the device Aggressive foreign substances in the combustion supply air can destroy or damage the heat gener...

Страница 19: ...nt Fig 5 Recommended space requirement Before installation 358 436 08 10 19 B A C C D Power HT 1 230 Power HT 1 280 Power HT 1 320 Dimensions A 80 cm 90 cm 100 cm Dimensions B 50 cm Dimensions C 50 cm...

Страница 20: ...he transport of the boiler to installation location manually push 2 sufficiently large steel pipes 1 not included through the carrying fixture Fig 6 Pos 2 so that the boiler can be lifted and transpor...

Страница 21: ...Before installation 358 436 08 10 21...

Страница 22: ...4 8 Application examples Application example 1 EC three with one pumped circuit and DHW preparation Hydraulic plan Before installation 22 358 436 08 10...

Страница 23: ...Wiring plan Before installation 358 436 08 10 23...

Страница 24: ...Application example 2 SEC three with one mixing heating circuit and DHW preparation Hydraulic plan Before installation 24 358 436 08 10...

Страница 25: ...Wiring plan Before installation 358 436 08 10 25...

Страница 26: ...Application example 3 EC three with three mixed circuits and DHW preparation Hydraulic plan Before installation 26 358 436 08 10...

Страница 27: ...Wiring plan Before installation 358 436 08 10 27...

Страница 28: ...Application example 4 Cascade with two EC three three mixed circuits hydraulic bypass and DHW preparation Hydraulic plan Before installation 28 358 436 08 10...

Страница 29: ...Wiring plan right EC three Before installation 358 436 08 10 29...

Страница 30: ...Wiring plan left EC three Before installation 30 358 436 08 10...

Страница 31: ...4 9 Legend Before installation 358 436 08 10 31...

Страница 32: ...er HT must be inserted through the opening in the rear or side wall If there is no drain underneath the condensate discharge the use of a suitable neutralisation plant and pump is necessary 5 3 Sealin...

Страница 33: ...Air Act 1993 the current Building Regulations must also be strictly observed The boiler should be installed in accordance with BS6644 with respect to protec ting the boiler from damage air for combus...

Страница 34: ...content 5 8 CO2 Content The CO2content in the exhaust gas must be checked during commissioning and during regular maintenance of the boiler as well as after reconstruction work on the boiler or on th...

Страница 35: ...0 35 Function Power HT 1 230 Power HT 1 280 Power HT 1 320 Boiler 2331 S 35 48 42 58 48 58 Nominal output prepurging 9504 S 77 1 89 3 97 7 110 3 103 9 115 5 Nominal output ignition 9512 S 77 1 89 3 97...

Страница 36: ...as reached the basic display again 3 Press information button The message Controller stop setpoint adjust appears in the display The actu al modulation degree will be displayed on the display 4 Press...

Страница 37: ...e CO 2 content is decreased Counter clockwise CO 2 content is increased 4 Replace safety cap on the adjusting screw for full load 2 Set CO2 content at min output 1 Power HT in the controller stop mode...

Страница 38: ...a contact opening width of at least 3 mm All connected components must comply to VDE Connecting lines have to be in stalled strain relieved Cable lengths Bus sensor cables do not carry mains voltage b...

Страница 39: ...erature sensor is located in the accessory bag For connection see wiring plan Replacing cables All connecting cables apart from the mains cable must be replaced when necessa ry withBAXI special cables...

Страница 40: ...between 1 0 and 2 5 bar Less than 0 5 bar Top up water Caution The maximum admissable installation pressure has to be considered Over 6 0 bar Do not start gas condensing boiler drain water Caution The...

Страница 41: ...f the boiler and the function of the safety devices The following should be pointed out the air inlet must not be restricted flammable materials and liquids must not be stored in the vicinity of the g...

Страница 42: ...8 OK button acknowledgment 2 Reset button 9 Information button 3 Reset safety temperature limiter STB 10 Rotating knob 4 Blanking plate 11 Chimney sweep button 5 Operator section ISR 12 ESC button 6...

Страница 43: ...ating operation will be carried out with the operating button Heating operation The selected setting will be mark ed with a bar underneath the operating mode symbol Boiler temp Automatic operation Aut...

Страница 44: ...ting limit is not activated DHW operation according to status 7 4 Setting up DHW operation Setting up DHW operation Boiler temp Switched on DHW will be prepared according to the selected switching pro...

Страница 45: ...6 Display information Various temperatures and messages can be called up by pushing the information button Including Room and outside temperature if sensor fitted Fault or service messages Note When...

Страница 46: ...e Setpoint manual control All pumps will be activated Ad ditional request will be ignored 1 Press OK button 2 Select menu point Maintenance service 3 Press OK button 4 Select parameters Manual control...

Страница 47: ...levels and is protected by a password Menu points Time and date Operator section Radio Time prog heating circuit 1 Time prog heating circuit 2 Time program 3 HC3 Time program 4 DHW Time program 5 Hol...

Страница 48: ...ing by the setting of time and date Basic display Boiler temperature Press Select with the menu point time and date Time and date Operator section Acknowledge selection with Select with the menu point...

Страница 49: ...ation mode button to return to the basic display Boiler temperature The previous menu point will be called up by pressing the ESC button without ta king over previously modified values If no settings...

Страница 50: ...n This parameter is only visible in the room device Language 20 Eu English Info Temporarily Permanently 22 E Temporarily Display of errors Code Code and text 23 E Code and text Contrast of display 25...

Страница 51: ...ery Delete device 134 C missing Operator unit 1 Missing Ready No reception Change battery Delete device 135 C missing Operator unit 2 Missing Ready No reception Change battery Delete device 136 C miss...

Страница 52: ...Time program 4 DHW Pre selection Mo Su Mo Su Mo Fr Sa Su Mo Tu We Th Fr Sa Su 560 Eu Mo Su 1st phase on 561 Eu 05 00 h min 1st phase off 562 Eu 22 00 h min 2nd phase on 563 Eu h min 2nd phase off 564...

Страница 53: ...ting circuit 1 Protection Automatic Reduced Comfort 700 Eu Automatic Comfort setpoint 710 Eu 20 0 C Reduced setpoint 712 Eu 16 0 C Frost protection setpoint 714 Eu 10 0 C Heating curve slope 720 Eu 1...

Страница 54: ...speed min 882 C 0 Pump speed max 883 C 100 Curve readj at 50 speed 888 E 33 Flow setp readj speed ctrl No Yes 890 E Yes Operating level changeover Frost protection Reduced Comfort 898 E Reduced Optg...

Страница 55: ...nually 1151 E 25 C Floor curing setp current 1155 E 0 Floor curing day current 1156 E 0 Excess heat draw Off Heating mode Always 1161 E Always With buffer storage tank No Yes 1170 E Yes With prim cont...

Страница 56: ...end 1401 E 15 C Continuous pump operation No Yes 1409 E No Overtemp prot pump circuit Off On 1420 E ON Mixing valve boost 1430 E 5 C Actuator running time 1434 E 120 s Floor curing function Off Functi...

Страница 57: ...riday Saturday Sun day 1642 F Monday Legionella funct time 1644 F Legionella funct setpoint 1645 F 65 C Legionella funct duration 1646 F 30 min Legionella function circ pump Off On 1647 F ON Circulati...

Страница 58: ...Yes Primary contr system pump Flow temp setpoint min 2110 F 8 C Flow temp setpoint max 2111 F 80 C Syst pump on heat gen lock Off On 2121 F Off Mixing valve boost 2130 F 10 C Actuator running time 213...

Страница 59: ...s Switching diff on HCs 2454 E 4 C Switching diff off min HCs 2455 E 5 C Switching diff off max HCs 2456 E 7 C Switching diff on DHW 2460 E 5 C Switching diff off min DHW 2461 E 6 C Switching diff off...

Страница 60: ...or start function Off 3833 E 19 00 h min Collector start funct grad 3834 E min C Collector frost protection 3840 E C Collector overtemp prot 3850 E C Evaporation heat carrier 3860 E Antifreeze None Et...

Страница 61: ...n hydraulic system Charge push forward time 5011 E 01 00 min Flow setpoint boost 5020 E 18 C Transfer boost 5021 E 10 C Type of charging Recharging Full charging Full charging legio Full charg 1st tim...

Страница 62: ...s Full charging with B36 No Yes 5146 E Yes Min start temp diff Q33 5148 E 3 C Excess interm circ temp del 5151 E 30 s Configuration Heating circuit 1 Off On 5710 C ON Heating circuit 2 Off On 5715 C...

Страница 63: ...or sensor B6 DHW circulation sensor B39 Buffer sensor B4 Buffer sensor B41 Common flow sensor B10 Solid fuel boiler sensor B22 DHW charging sensor B36 Buffer sensor B42 Common return sensor B73 Cascad...

Страница 64: ...t discharge Release swi pool solar Operating level DHW Operating level HC1 Operating le vel HC2 Operating level HC3 Room thermostat HC1 Room ther mostat HC2 Room thermostat HC3 DHW thermostat Pulse co...

Страница 65: ...st VK1 Consumer requ est VK2 Consumer request VK3 Excess heat discharge Release swi pool solar Operating level DHW Operating level HC1 Operating level HC2 Operating level HC3 Room thermostat HC1 Room...

Страница 66: ...12 E Check no heat source 2 6213 E Check no storage tank 6215 E Check no heating circuits 6217 E Software version 6220 E LPB system Device address 6600 C 0 Bus power supply function Off Automatic 6604...

Страница 67: ...diagnostic code 2 Burner control phase 2 6815 E History 3 Date Time Error code 6820 E SW diagnostic code 3 Burner control phase 3 6825 E History 20 Date Time Error code 20 6990 E SW diagnostic code 2...

Страница 68: ...put QX2 Relay output QX3 Relay output QX21 module 1 Relay output QX22 modu le 1 Relay output QX23 module 1 Relay output QX21 module 2 Re lay output QX22 module 2 Relay output QX23 module 2 Relay out p...

Страница 69: ...e source 1 Missing Faulty Manual control active Heat generation lock active Chimney sweep funct active Temporarily unavailable Outside temp limit active Not released Released 8100 C Priority state sou...

Страница 70: ...state source 1 prog no 8100 8128 C Priority state source 16 Parameters see Priority state source 1 prog no 8100 8130 C Cascade flow temp 8138 C Cascade flow temp setp 8139 C Cascade return temp 8140...

Страница 71: ...iler 8570 C Diagnostics consumers Outside temperature 8700 Eu Outside temperature minimum 8701 Eu Outside temperature maximum 8702 Eu Outside temp attenuated 8703 E Outside temp composite 8704 E Heati...

Страница 72: ...m circ pump 8826 E DHW temp 1 8830 C DHW temp setpoint 8831 C DHW temp actual value bottom B31 8832 C DHW circulation temp 8835 E DHW charging temp 8836 E Flow temp setpoint Consumer circuit1 8875 C F...

Страница 73: ...odule 3 Off On 9058 C Burner control Prepurge time 9500 E 10 s Nominal output prepurging 9504 E 0 kW Nominal output ignition load 9512 E 0 kW Nominal output Partial load 9524 E 0 kW Nominal output ful...

Страница 74: ...me will be set under program number 6 The time changing will be car ried out on the Sunday following the set date Operator section Language 20 The language of the menu guidance can be modified under p...

Страница 75: ...s setting is provided for the pure operation without room functions and is not needed in connection with this controller service unit this setting is used for example to secure or save control setting...

Страница 76: ...s will automatically be ta ken over for all 3 on off phases in this day group Heating phases 501 to 506 521 to 526 541 to 546 561 to 566 601 to 606 Up to three heating phases may be set per heating ci...

Страница 77: ...om temperature during the frost protection operation Without room sensor or with the room influence prog no 750 1050 1350 this value is used for calculation of the flow temperature to theoretically re...

Страница 78: ...radient becomes obsolete For automatic adaptation of the heating curve a room sensor must be connected The value for room influence see prog no 750 1050 1350 must be set between 1 and 99 Should there...

Страница 79: ...uous comfort temperature and continuous reduced temperature this function is not activated Flow temp setpoint limitati ons Minimum 740 1040 1340 Maximum 741 1041 1341 With this function a range can be...

Страница 80: ...etc the higher the value can be set and the room tempera ture is taken into consideration even more Caution Open radiator valves Should there be radiator valves in the leading room assembly location o...

Страница 81: ...otection mode During the quick setback the heating circuit pump is turned off and the mixing valve is also closed during mixing circuits During the quick setback no heat requi rement is sent to the he...

Страница 82: ...room unit With a room unit the conversion of the operating level compared to the programmed time point is moved forward so that the buil ding dynamics heat up and cool down time is considered In this...

Страница 83: ...ating circuit pump boiler pump can be switched off by quick setback or reaching the room set point Yes the heating circuit pump boiler pump remains switched on even during the quick setback and after...

Страница 84: ...Ch X Starting day Fh Functional heating Ch Curing heating Important The respective regulations and standards of the screed manufacturer have to be observed A correct function is only possible with a c...

Страница 85: ...ting level With this option the speed of the heating circuit pump is calcula ted acc to the operating level The pump is controlled in operating level comfort incl optimization or during active floor c...

Страница 86: ...ill be continuously controlled to the nominal drinking water temperature value independent from the time switching pro grammes Time programs HCs The DHW temperature will be switched over between the n...

Страница 87: ...ll be activated on a certain weekday prog no 1642 Legionella funct periodically 1641 Setting the interval for the legionella function periodically recommended setting in case of additional drinking wa...

Страница 88: ...s am F hler w hrend der eingestellten Verweildauer Prog Nr 1646 eingehalten werden Die Einstellung des Zirkulationssollwerts wird nach oben vom Nennsollwert begrenzt Optg mode changeover 1680 Using ex...

Страница 89: ...100 C0004840 TVmax TVmin TVw TVmax Flow temp setpoint max TVmin Flow temp setpoint min TVw Current Flow temp setpoint Syst pump on heat gen lock 2121 This parameter can set whether during active heat...

Страница 90: ...after DHW mode 2253 The delay times of the pumps are controlled according to heating mode or drin king water mode Boiler pump at heat generati on lock 2301 Stop of boiler pump in case of activated he...

Страница 91: ...speed During high boiler output the boiler pump should run on high speed Pump speed min 2322 For the modulating pump the working range can be defined in percent of output The control translates the p...

Страница 92: ...se of the firing automation by the controller this remains on the set output for a specified time Only after this time has elap sed is the modulation released Prog no 2450 is used to set at which oper...

Страница 93: ...r Early on late off additional boiler is switched on as early as possible output range min and back off as late as possible output range min I e boiler in ope ration as much as possible or as long as...

Страница 94: ...erence between the flow and return sensor is smaller than the minimal temperature spread set here a source is switched off as early as possible independently of the set lead strate gy If the temperatu...

Страница 95: ...3822 For several combined exchangers in the system the loading sequence for the combined storage tank can be defined by setting the loading priority None each storage tank is loaded alternately for a...

Страница 96: ...ircuit the operation of the secondary pump of the heat exchanger can be delayed Collector start function 3830 If the temperature at the collector with the pump turned off not be measured correctly e g...

Страница 97: ...ement Pulse valency 3887 Defines the flow per pulse for the H4 inlet The H4 inlet must be configured to pulse count for this Solid fuel boiler Locks other heat sources 4102 Locks other heat sources 41...

Страница 98: ...rative tem perature Setpoint min The value set in prog no 4110 is used as comparative temperature Pump after run time 4140 Pump after run time 4140 Setting pump after run time Buffer storage Auto gene...

Страница 99: ...Recooling collector 4757 Recooling with a too high buffer storage tank temperature by transmission of energy to the environment via the collector area Off recooling is switched off Summer the recoolin...

Страница 100: ...ff Heating Mode The full charging is active if the automatic heat source block blocks the heat source during valid heat request based on the buffer temperatu re If the buffer storage tank reaches the...

Страница 101: ...g is started The DHW charging is ended if the temperature of the current setpoint is reached At the first DHW release of the day a forced charging is performed The DHW charging is also started if the...

Страница 102: ...e 5061 24h day Permanent release of the electric insert DHW release Release of the electric insert depending on DHW release see prog no 1620 Time programme 4 Release of the electric insert via the tim...

Страница 103: ...e Tv determines how long a spontaneous change of the con trol difference continues to have an effect A short time only influences the con trol variable only for a short time Transfer strategy 5130 The...

Страница 104: ...cuit pump Configuration Heating circuit 1 2 5710 5715 The heating circuits can be switched on or off by this setting The parameters for the heating circuits are hidden in the switched off state This a...

Страница 105: ...and heating circuit 1 however not for heating circuits 2 and 3 or for the external consumer circuit All requests the diverting valve is connected hydraulically for all requests and switches between DH...

Страница 106: ...r cir cuit for connection to a solid fuel boiler Time program 5 K13 The relay will be controlled by the time program 5 accor ding to the settings Buffer return valve Y15 This valve must be configured...

Страница 107: ...buffer storage tank sensor Buffer st tank sensor B41 centre buffer sensor Flue gas temp sensor B8 Flue gas temp sensor for the alarmfunction Common flow sensor B10 common flow sensor for boiler casca...

Страница 108: ...oom thermostat request can be gene rated for the set heating circuit DHW thermostat Connection of the DHW thermostat Pulse count By querying the input the low frequency pulse e g for flow measu rement...

Страница 109: ...menu point Solar Primary contr system pump For this usage the respective settings can be adjus ted in the menu point Primary contr system pump Relay output QX21 QX23 6030 6038 Relay outputs for the mo...

Страница 110: ...ted Heating circuit pump HC2 Q6 the heat circuit pump HC2 will be activated Heating circuit pump HC3 Q20 the heat circuit pump HC3 will be activated Collector pump Q5 a circulation pump for the collec...

Страница 111: ...rature is between 5 C and 1 5 C the pump will be activated every 6 hours for 10 minutes When rea ching the upper limit of 1 5 C the pump will be switched off Saving sensors 6200 Sensor statuses can be...

Страница 112: ...Charging pump solar connection Heat gen shutoff valve 13 Diverting valve 14 Diverting valve solar connection 16 Primary control without exchanger 17 Primary control 1 exchanger 19 Intermediate circui...

Страница 113: ...e transmitted via LPB to be suppres sed on connected operating elements Alarm delay 6612 Settling out of the alarm on the BM module can be delayed in the base device by an adjustable time This allows...

Страница 114: ...ltaneously the system time is adapted since the change is done by the mas ter The time of the controller is then continually adapted to the system time Master The time of day can be modified at the co...

Страница 115: ...n for display and reset of the burner ionisation current service alarm The service alarm can only be reset if the reason for service is taken care of Chimney sweep function 7130 The chimney sweep func...

Страница 116: ...occurs PStick progress 7253 The read or write progress is displayed as a percentage If no operation is active or an error shows up 0 is displayed State PStick 7254 No stick The LMS control detected no...

Страница 117: ...p prot active Restricted boiler protection Restricted DHW priority Restricted buffer Forced draw Forced draw DHW Forced draw source Overrun active Comfort heating mode Opt start ctrl boost heating Opt...

Страница 118: ...d max charging temp Forced legionella setp Forced nominal setp Charg el imm heater El charging legionella setp El charging nominal setp El charging reduced setp El charging frost prot setp El imm heat...

Страница 119: ...ode Min limitation active Min limitation Min limitation part load Min limitation active In operation Protective start Protective start part load Return limitation Return limitation part load Charging...

Страница 120: ...prot active Overtemp prot active Overtemp prot active Max charging temp reached Max charging temp reached Charging DHW buffer swi pool Charging DHW buffer swi pool Charging DHW buffer Charging DHW buf...

Страница 121: ...p for HC In operation for DHW In operation for DHW In part load op for DHW In part load op for DHW In op for HC DHW In op for HC DHW In part load op for HC DHW In part load op for HC DHW Overrun activ...

Страница 122: ...arged forced temp Charged required temp Part charged required temp Charged min charging temp Cold Cold No request No request The following messages are possible under swimming pool End user E Commissi...

Страница 123: ...eter must only be changed by a heating specialist Conversion fan output speed increase 9626 Conversion fan output speed Y section 9627 With this parameter the rotational speed of the fan can be adjust...

Страница 124: ...viced Clean burner areas and heating surfaces Replace wear parts see Spare parts list Caution Only original spare parts must be used Check connection and seal locations of water filled parts Check saf...

Страница 125: ...10 125 flue gas connection Ignition transformer below the control unit Ignition electrodes Venturi tube Silencer Gas valve Syphon boiler control lms ionization electrode sight glass below the control...

Страница 126: ...Fig 30 Boiler view Maintenance 126 358 436 08 10 gas connection supply air conntection heating return heating flow...

Страница 127: ...nsing boiler 3 Release ignition cable ionisation line and earthing cable 4 Disconnect connection lines from fan and gas valve Fig 31 Loosen screws on the exhaust silencer 2 1 C0004594 5 Remove screws...

Страница 128: ...0 7 Remove nuts and washers and pull out the entire burner 5 with burner seal 6 forwards Installing burner The installation of the burner is done in the opposite sequence Note Use new seals when insta...

Страница 129: ...ler must be shut off and it must be secured from accidentally being switched back on Fig 34 Remove ignition electrode block 2 1 1 Loosen ignition cable 2 Remove nuts and pull out the ignition electrod...

Страница 130: ...electric shock Do not touch plug contacts during the ignition process Changing the ionisation electrode Danger of electric shock Before performing service work power to the boiler must be shut off and...

Страница 131: ...urner see section Installing and removing burner Fig 37 Dismantle burner pipe C0004611 1 2 2 Remove screws and remove burner pipe 1 with the burner pipe seal 2 3 Clean the burner pipe with compressed...

Страница 132: ...he cover of the exhaust collection pan 1 2 C0004618 2 Remove screws and remove cover 1 of the exhaust collection pan with seal 2 Fig 39 Heat exchanger 3 C0004619 3 Clean heat exchanger 3 with a brush...

Страница 133: ...hon 4 and clean 6 Clean siphon 7 Reinstall siphon 8 Replace the cover of the exhaust collection pan Note Use a new seal when installing the cover 9 Reinstall burner see section Installing and removing...

Страница 134: ...n with compressed air 5 Reassemble burner in the opposite sequence Note Use new seals when reassembling the burner 6 Reinstall burner see section Installing and removing burner 9 10 Control and regula...

Страница 135: ...he dis play on the operating panel points out the cause of the disturbance see section 9 12 Fault code table Burner does not start no voltage at the control and regulating centre no Burner ON signal f...

Страница 136: ...nsor fault Check connection inform heating specialist1 54 Flow temperature DHW sensor fault 57 Drinking water circulation temperature sensor fault 60 Room temperature 1 sensor fault 65 Room temperatur...

Страница 137: ...re occurs several times contact heating specialist lack of gas polarity of mains connection safe ty period check ignition electrode and ionisation current 1 3 146 Configuration fault Common message 15...

Страница 138: ...351 Prim sys pump addr err 352 Pr less header addr err 353 Common flow sensor B10 missing 371 Flow temperature 3 Heating circuit 3 monito ring 372 Limit thermostat HC3 373 Expansion module 3 fault co...

Страница 139: ...sts TW1 TW2 TVZ Ignition phase Ignition and start of safety period flame forming Ionisation current build up TSA1 Safety time constant Flame monitoring with ignition TSA2 Safety time variable Flame mo...

Страница 140: ...from safety valve 41 E ECO 43 Emergency operation 46 Error message 45 F Factory settings 75 34 Fault 135 Fault code table 136 Fault message 133 34 Fault message 43 Floor curing function 84 Flue lenght...

Страница 141: ...ctory setting 46 Room influence 80 Room temperature 41 Comfort setpoint 44 Reduced setpoint 45 S Safety valve 32 124 Servicing message 43 Software version 75 Spare parts 124 Standards 7 State 117 Stra...

Страница 142: ...Space for notes 142 358 436 08 10...

Страница 143: ...Space for notes 358 436 08 10 143...

Страница 144: ...Technical data and errors are subject to change Specification nonbinding Baxi S p A 36061 Bassano del Grappa VI Italy Via Trozzetti 20 Tel 39 0424 517111 Fax 39 0424 38089 www baxi it...

Отзывы: