9.5 Check and replacing
ionisation electrode
The ionisation electrode must always be in contact with the flame. During burner
operation, the measured ionisation flow must following data display:
- At minimum power > 5 µA DC (switching threshold at 0.7 µA DC)
- At maximum power > 10 µA DC
Measurement ionization current
For measurement of the ionisation current, pull plug from the gas-firing automa-
ton and connect amperemeter between plug and electrode.
Danger of electric shock!
Do not touch plug contacts during the ignition process!
Changing the ionisation electrode
Danger of electric shock!
Before performing service work, power to the boiler must
be shut off and it must be secured from accidentally being switched back on!
Fig. 35: Removing ionisation electrode
1
2
1. Release ionisation line
2. Remove nuts and pull out the ionisation electrode (1) with the seal (2)
3. Insert the new ionisation electrode with seal and fasten with nuts
Note: Installation position and electrode clearance has to be maintained according
to
Fig. 36
4. Reconnect the ionisation line
Maintenance
130
358 436 08.10
Power HT 1.230 - 1.280 - 1.320
Содержание LUNA HT 1.280
Страница 1: ...Installation operation and maintenance manual Condensing gas boiler Power HT 1 230 1 280 1 320...
Страница 8: ...2 6 Conformity declaration Safety 8 358 436 08 10...
Страница 10: ...Technical Data 10 358 436 08 10...
Страница 12: ...Technical Data 12 358 436 08 10...
Страница 13: ...3 3 Wiring Diagram Fig 2 Wiring Diagram Technical Data 358 436 08 10 13...
Страница 21: ...Before installation 358 436 08 10 21...
Страница 23: ...Wiring plan Before installation 358 436 08 10 23...
Страница 25: ...Wiring plan Before installation 358 436 08 10 25...
Страница 27: ...Wiring plan Before installation 358 436 08 10 27...
Страница 29: ...Wiring plan right EC three Before installation 358 436 08 10 29...
Страница 30: ...Wiring plan left EC three Before installation 30 358 436 08 10...
Страница 31: ...4 9 Legend Before installation 358 436 08 10 31...
Страница 126: ...Fig 30 Boiler view Maintenance 126 358 436 08 10 gas connection supply air conntection heating return heating flow...
Страница 142: ...Space for notes 142 358 436 08 10...
Страница 143: ...Space for notes 358 436 08 10 143...