With buffer storage tank
(5090)
-
No
: The domestic hot water storage tank will be directly charged from the boi-
ler.
-
Yes
: The domestic hot water storage tank will be charged from the buffer stora-
ge tank.
With primary control/system
pump
(5092)
-
No
: the domestic hot water storage tank will be charged without primary con-
troller/system pump.
-
Yes
: the domestic hot water storage tank will be charged from the primary con-
troller on/with the system pump.
With solar integration
(5093)
This function sets whether the DHW storage tank should be filled.
Pump speed limitations
(5101, 5102)
Setting of the minimum and maximum speed of the storage tank charging pump
in percent.
Speed Xp
(5103)
The P-band Xp defines the amplification of the controller A smaller Xp value leads
to a higher actuation of the charging pump with equal control difference.
Speed Tn
(5104)
The reset time Tn determines the reaction speed of the controller when compen-
sating for remaining controller differences. A shorter reset time Tn leads to faster
compensating.
Speed Tv
(5105)
The preholding time Tv determines how long a spontaneous change of the con-
trol difference continues to have an effect. A short time only influences the con-
trol variable only for a short time.
Transfer strategy
(5130)
The transfer is always allowed or to the set DHW release times.
Interm circ boost recharging
(5139)
Setpoint boost for charging setpoint on charging sensor B36 with recharging.
Intermediate circuit boost
(5140)
Setpoint boost for charging setpoint on charging sensor B36 with full charging.
Excess interm circ temp max
(5141)
With this parameter the end criterion of a full charging during control is specified
on the charging sensor B36. If the contents of the layer storage is charge to the
bottom, the temperature increases on the charging sensor
Flow setp compensation de-
lay
(5142)
The filter time for the setpoint lead is set here.
Flow setp compensation Xp
(5143)
The P-band Xp defines the amplification of the controller A smaller Xp value leads
to higher actuation of the charging pump with equal control difference.
Flow setp compensation Tn
(5144)
The reset time Tn determines the reaction speed of the controller when compen-
sating for remaining controller differences. A shorter reset time Tn leads to faster
compensating.
Programming
358 436 08.10
103
Содержание LUNA HT 1.280
Страница 1: ...Installation operation and maintenance manual Condensing gas boiler Power HT 1 230 1 280 1 320...
Страница 8: ...2 6 Conformity declaration Safety 8 358 436 08 10...
Страница 10: ...Technical Data 10 358 436 08 10...
Страница 12: ...Technical Data 12 358 436 08 10...
Страница 13: ...3 3 Wiring Diagram Fig 2 Wiring Diagram Technical Data 358 436 08 10 13...
Страница 21: ...Before installation 358 436 08 10 21...
Страница 23: ...Wiring plan Before installation 358 436 08 10 23...
Страница 25: ...Wiring plan Before installation 358 436 08 10 25...
Страница 27: ...Wiring plan Before installation 358 436 08 10 27...
Страница 29: ...Wiring plan right EC three Before installation 358 436 08 10 29...
Страница 30: ...Wiring plan left EC three Before installation 30 358 436 08 10...
Страница 31: ...4 9 Legend Before installation 358 436 08 10 31...
Страница 126: ...Fig 30 Boiler view Maintenance 126 358 436 08 10 gas connection supply air conntection heating return heating flow...
Страница 142: ...Space for notes 142 358 436 08 10...
Страница 143: ...Space for notes 358 436 08 10 143...