Flow setp compensation Tv
(5145)
The preholding time Tv determines how long a spontaneous change of the con-
trol difference continues to have an effect. A short time only influences the con-
trol variable only for a short time.
Full charging with B36
(5146)
Here it can be set whether the end of the full charging is detected via the tempe-
rature on the charging sensor B36.
-
No
: the end of the full charging is detected via the temperature on the upper
and lower storage sensor B3 and B31.
-
Yes
: the end of the full charging is detected via the temperature on the upper
storage sensor B3.
Min start temp diff Q33
(5148)
This parameter determines switch on delay of the intermediate circuit pump de-
pending on the boiler temperature. The intermediate circuit pump is switched on
as soon as the boiler temperature has reached the boiler setpoint plus the value
set here. The setting -5 °C has the effect that the intermediate circuit pump will
be switched on as soon as the boiler temperature has reached the boiler setpoint
up to 5 °C.
Excess interm circ temp del
(5151)
Control of the burner output on the charging temperature is activated if the time
set here has elapsed since switching on the intermediate circuit pump.
Configuration
Heating circuit 1,2
(5710, 5715)
The heating circuits can be switched on or off by this setting. The parameters for
the heating circuits are hidden in the switched off state.
This adjustment directly affects the heating circuits and has no influence on the
operating unit!
DHW sensor
(5730)
-
None
: No DHW sensor available.
-
Sensor B3
: It exists a DHW storage tank sensor. The controller calculates the
switching points with the corresponding switching difference from the DHW
setpoint and the measured DHW storage tank temperature.
-
Thermostat
: Control of domestic hot water temperature as a function of the
switching status of a thermostat connected to DHW sensor B3.
Note:
When using a DHW thermostat no reduced mode is possible. This means if
reduced mode is active, the DHW preparation is blocked with the thermostat.
Caution! No frost protection for DHW !
The domestic water frost protection cannot be guaranteed.
-
Sensor B38
: An instantaneous heater discharge sensor is present. The controller
calculates the switching points with corresponding switching difference from
the instantaneous heater setpoint and the measured DHW discharge tempera-
ture.
DHW control element Q3
(5731)
-
None
: DHW-charge de-activated via Q3.
-
Charge pump
: DHW-charging via the connection of a charge pump to Q3/Y3.
-
Deflecting valve
: DHW-charging via connection of a deflecting valve at Q3/Y3.
Programming
104
358 436 08.10
Содержание LUNA HT 1.280
Страница 1: ...Installation operation and maintenance manual Condensing gas boiler Power HT 1 230 1 280 1 320...
Страница 8: ...2 6 Conformity declaration Safety 8 358 436 08 10...
Страница 10: ...Technical Data 10 358 436 08 10...
Страница 12: ...Technical Data 12 358 436 08 10...
Страница 13: ...3 3 Wiring Diagram Fig 2 Wiring Diagram Technical Data 358 436 08 10 13...
Страница 21: ...Before installation 358 436 08 10 21...
Страница 23: ...Wiring plan Before installation 358 436 08 10 23...
Страница 25: ...Wiring plan Before installation 358 436 08 10 25...
Страница 27: ...Wiring plan Before installation 358 436 08 10 27...
Страница 29: ...Wiring plan right EC three Before installation 358 436 08 10 29...
Страница 30: ...Wiring plan left EC three Before installation 30 358 436 08 10...
Страница 31: ...4 9 Legend Before installation 358 436 08 10 31...
Страница 126: ...Fig 30 Boiler view Maintenance 126 358 436 08 10 gas connection supply air conntection heating return heating flow...
Страница 142: ...Space for notes 142 358 436 08 10...
Страница 143: ...Space for notes 358 436 08 10 143...