Troubleshooting and rectification
Operation Manual
b maXX safe PLC
BMC-M-SAF-02
Document no.: 5.07020.04
87
14
14.6 Exchanging devices
If a defect in the safety system is detected, the safety control will have to be taken out of
operation immediately. If a memory card with a complete copy of the application and con-
figuration data for the affected safety control is available, the safety control can be re-
placed with a new safety control without having to use the safe programming interface.
The following prerequisites will have to be fulfilled in order to exchange the device without
the use of the safe programming environment:
Once the device has been exchanged and the data from the memory card has been cop-
ied to the control, an appropriate spot check type function test will have to be conducted
for the system. This must be documented accordingly.
If the project data is loaded without a renewed compilation of the control system, a spot
check type function test will be sufficient. In doing so, it must be ensured that the alloca-
tion of the project data is correct by means of organizational measures.
For the handling of defective component groups, see the chapter
CAUTION!
m
There is a memory card available with contents which guarantee a 1:1 copy of the
applicable system by means of complying with organizational measures.
m
No further changes in the configuration of the system may be made during the ex-
change of the device.
m
The procedure of transferring data from the card to the control described in the
chapter
Data transfer from the card to the control
be followed.
m
The safety instructions related to memory cards in accordance with the chapter
Safety-related instructions on the use of memory cards
must be complied with.
CAUTION!
If there is no memory card with a definite copy of the control data available, the com-
missioning of the safety control will only be permissible by means of the ProSafety
safe programming environment.
If the project is recompiled before being transferred to the control, a complete valida-
tion in accordance with the chapter
from page 79 onward will
be required.
Содержание b maXX BMC-M-SAF-02
Страница 8: ...Operation Manual b maXX safe PLC BMC M SAF 02 Document no 5 07020 04 Baumüller Nürnberg GmbH 8 of 118 ...
Страница 16: ...Operation Manual b maXX safe PLC BMC M SAF 02 Document no 5 07020 04 Baumüller Nürnberg GmbH 16 of 118 ...
Страница 58: ...Operation Manual b maXX safe PLC BMC M SAF 02 Document no 5 07020 04 Baumüller Nürnberg GmbH 58 of 118 ...
Страница 82: ...Operation Manual b maXX safe PLC BMC M SAF 02 Document no 5 07020 04 Baumüller Nürnberg GmbH 82 of 118 ...
Страница 90: ...Operation Manual b maXX safe PLC BMC M SAF 02 Document no 5 07020 04 Baumüller Nürnberg GmbH 90 of 118 ...
Страница 92: ...Operation Manual b maXX safe PLC BMC M SAF 02 Document no 5 07020 04 Baumüller Nürnberg GmbH 92 of 118 ...
Страница 100: ...Operation Manual b maXX safe PLC BMC M SAF 02 Document no 5 07020 04 Baumüller Nürnberg GmbH 100 of 118 A ...
Страница 119: ......