Electrical data
Instruction handbook
b maXX
5800
Document No. 5.16027.04
Baumüller Nürnberg GmbH
40
3.4
1)
All rated values are based on a DC link voltage of 640 V, a control voltage of 24 V and a surrounding tem-
perature of 40 °C and the switching frequency specified.
2)
The input current must be reduced between 40 °C and 55 °C, refer to correction values at changed operation
conditions
3)
The output voltage is a pulsed direct voltage. The adjusting range is based on the RMS-value of the funda-
mental wave.
4)
The range of the output frequency is based on a stationary operation in the linear range of the PWM, i. e.
without overmodulation.
The quality of the generated output voltages depends on the ratio between output frequency and current con-
troller frequency f
I-R
( f
I-R
= 1/cycle time current controller).
The maximum output frequency f
max
, generated with high quality, is calculated as follows:
f
max
f
I-R
K
pf
--------
, typical K
Pf
18
=
Furthermore the controller sets an upper limit for the output frequency of 599 Hz (please contact the respon-
sible Baumüller sales department, keyword: export restriction).
PWM frequency
Current controller
cycle time
Range of the output frequency
2 kHz
250 µs
0 - 225 Hz
4 kHz
125 µs
0 - 450 Hz
8 / 16 kHz
62.5 µs
0 - 599 Hz (900 Hz
*)
)
*)
900 Hz could be generated by the controller
The device is able to generate output voltages with frequencies between f
max
and 599 Hz and the controller
allows that, however the quality of this voltages cannot be guaranteed.
Typical the devices are marked with the max output frequency at 4 kHz switching frequency: 0 ... 450 kHz.
5)
The device supplies the rated/peak currents at rated DC link voltage.
The output currents must be reduced accordingly when operating with a DC link voltage is higher than 640
V and output power remains constant, refer to
Derating: Output current as function of the DC link voltage
6)
The actual possible overload time depends on the preloading of the device and the heat sink temperature
and is detected by the overload monitoring of the device.
Assumption: initial conditions before the overload occurrence: heat sink temperature 40 °C, I = 0 A,
7)
Without loads on the digital outputs and motor brake.
8)
Short-circuit protected for a maximum of 1 minute.
9)
This power rating is the total power rating of both axes.
10)
120 s for BM5807-SG-, refer to
11)
The continuously permitted output current must be reduced complying with
on page 41, if the statical output frequency is lower than 15 Hz and the frequency remains
between 0 and 15 Hz for over 5 seconds.
12)
The input current of the 24 V power supply is limited to 16 A when using a BM5800 multi-axis controller. If
several double axis modules with several brakes are used, the maximum brake current of all integrated
axis modules is limited to 12 A, refer to
NOTE!
Содержание b maXX 5000 BM5800 Series
Страница 158: ...Recommissioning Instruction handbook b maXX 5800 Document No 5 16027 04 Baumüller Nürnberg GmbH 158 of 174 12 6 ...
Страница 164: ...Instruction handbook b maXX 5800 Document No 5 16027 04 Baumüller Nürnberg GmbH 164 of 174 ...
Страница 165: ...165 of 174 Operation Manual b maXX 5800 Document no 5 16027 04 APPENDIX B DECLARATION OF CONFORMITY ...
Страница 168: ...Operation Manual b maXX 5800 Document no 5 16027 04 Baumüller Nürnberg GmbH 168 of 174 ...
Страница 174: ...Instruction handbook b maXX 5800 Document No 5 16027 04 Baumüller Nürnberg GmbH 174 of 174 Notes ...
Страница 175: ......