Installation altitude H
k
H
Correction value installation altitude
Technical data
Instruction handbook
b maXX
5800
Document No. 5.16027.04
33
3
Figure 7:
Correction value k
H
in dependence on the installation altitude H
I
permitted
I
rated
k
T
k
H
=
The permitted output current I
permitted
(adjusted output rated current) is calculated accord-
ing following formula:
I
rated
=
Output rated current at 40 °C and up to 1000 m,
refer to
If k
T
.
k
H
> 1, then I
permitted
= I
rated
,
an output current higher than I
rated
is not possible.
NOTICE!
The following condition
must
always be met to prevent the device of overload:
If k
T
.
k
H
> 1, the operation of the device is permitted and I
permitted
is limited to I
rated
.
k
T
k
H
0,79