Installation
Instruction handbook
b maXX
BM3000, BM3200, BM3300
Document no. 5.11018.11
119
7
7.13 Connections BM3000
7.13.1 X100 input bridging relay
X100
7.13.2 Power connections
1U1, 1V1, 1W1
Power supply system
1U1
1V1
1W1
1C1
1D1
PE
1C1, 1D1
DC link
PE
PE-connection
Input current:
0.08 A
Level:
Low (0 ... 5 V); High (12 … 28 V)
1
Input bridging relay
2
not
connected
3
M24V
Max. conductor cross-section
Termination system
0.2 mm² to 1.5 mm²
spring clamp termination
1 2 3
Max. conductor cross-section
Termination system
Tightening torque
1 mm² bis 4 mm²
Cable lug for M4
min. 1.4 Nm
max. 1.8 Nm
NOTICE!
The DC link cables must be double isolated.