Fieldbus communication
Instruction handbook
b maXX
BM3000, BM3200, BM3300
Document no. 5.11018.11
Baumüller Nürnberg GmbH
164
8.6
8.6.4
POWERLINK
®
.
Type code
BM3200, BM3300
with POWERLINK
®
:
BM3XXX-XXXX-XXXXX[-X]-
4
XXXX[-S0X]-XX[-XX][-EXX][-#XX]
BM3200, BM3300
devices can communicate with a POWERLINK
®
Managing Node via
the fieldbus connection POWERLINK
®
.
X3
and
X4
on the front side of the device are the RJ45 connections for POWERLINK
®
(also see
Mounting and in-
stallation
.
The mounting/installation consists of the following steps:
1
De-energize the
BM3200, BM3300
device
2
Set the
BM3200, BM3300
IP-address,
.
3
Connect
BM3200, BM3300
with Ethernet-connection cables.
n
Please, observe an EMC-compatible laying of the Ethernet connection cables!
n
The following cables were released for use by Baumüller:
Ethernet-connection cable;
Further information see
Cables - EtherCAT®, VARAN, POWERLINK® .
181.
Commissioning
The following preconditions must be fulfilled before commissioning:
1 BM3200, BM3300
with POWERLINK
®
is installed correctly.
n
Ethernet-connection cables are wired correctly.
2
The control cabinet is properly locked and all safety devices are operating.
3
The
BM3200, BM3300
device is ready-to-use.
Address switch
By means of the address switches S3 and S4 the last byte of the IP-address is set
(See settings
IP address 192.168.100.0 is not allowed.
Further information about the setting possibilities of the POWERLINK
®
Controlled Node
see „Application Manual“.
Parameters
The parameter settings determine the behavior of the POWERLINK
®
Controlled Node in
operation. Parameters are set with the software ProDrive.
1
Start ProDrive
2
Click on „Project Tree“.
3
Communication settings with ProDrive
n
Project Tree: Configuration/Fieldbus Slave
(refer also Parameter manual
BM3200, BM3300
)
m
set Synchronization to „On“
m
SYNC time = Fieldbus cycle time = POWERLINK
®
cycle time = 500 µs to 8 ms
This setting is not necessary if using the POWERLINK
®
profile and the POWER-
LINK
®
Managing Node sets a valid value in object 0x1006 „Communication cycle
period“.
Содержание b maXX 3000
Страница 67: ...Design and Function Instruction handbook b maXX BM3000 BM3200 BM3300 Document no 5 11018 11 67 of 218 4 ...
Страница 208: ...Instruction handbook b maXX BM3000 BM3200 BM3300 Document no 5 11018 11 Baumüller Nürnberg GmbH 208 of 218 A ...
Страница 209: ...209 of 218 Instruction handbook b maXX BM3000 BM3200 BM3300 Document no 5 11018 11 APPENDIX B DECLARATION OF CONFORMITY ...
Страница 212: ...Instruction handbook b maXX BM3000 BM3200 BM3300 Document no 5 11018 11 Baumüller Nürnberg GmbH 212 of 218 ...
Страница 218: ...Instruction handbook b maXX BM3000 BM3200 BM3300 Document no 5 11018 11 Baumüller Nürnberg GmbH 218 of 218 Notes ...
Страница 219: ......