Menu Screens and Password Levels
WR Series Unit
System Config: A1-A10 User (2000)
Adv. System Config: B1-B4 Technician (1313)
I/O Config: C1-C18 Technician (1313)
On/Off: User (2000)
Alarm Logs: User (2000)
Settings
Date/Time: Technician (1313)
Language: User (2000)
Network Config: Technician (1313)
Serial Ports: Technician (1313)
Initialization
Clear Logs: User (2000)
System Default: Engineer (9254)
Restart:
User
(2000)
Parameter Config: Engineer (9254)
Alarm Export: User (2000)
Logout: Used to log out of the current password
level. Entering back into the menu requires
password.
LC1000 Controller
System Config
General: User (2000)
Zone 1: User (2000)
Zone 2: User (2000)
Zone 3: User (2000)
Adv. System Config: B1-B13 Technician (1313)
I/O Configuration: C1-C10 Technician (1313)
On/Off: User (2000)
Alarm Log: User (2000)
Settings
Date/Time: Technician (1313)
Language: User (2000)
Network Config: Technician (1313)
Initialization
Clear Logs: User (2000)
System Default: Engineer (9254)
Restart:
User
(2000)
Parameter Config: Engineer (9254)
Alarm Export: User (2000)
Logout: Used to log out of the current password
level. Entering back into the menu requires
password.
ADDITIONAL INFORMATION
Setpoints
The
LC6000
setpoints will determine the cooling and
heating setpoints when
communicating with the wall-
mount units
. The
unit
cooling and heating setpoints
will determine the cooling and heating setpoints when
in stand alone mode
.
If at any time the unit(s) loses communication with the
LC6000 controller, the unit(s) will go into stand alone
mode.
Calibrating Sensors
1. Press MENU key on LC controller interface to go to
the Main Menu screen.
2. Use UP or DOWN keys and ENTER key to enter
USER password 2000.
3. Press UP or DOWN keys to scroll to
I/O Config
;
press ENTER key.
4. Press UP or DOWN keys to scroll to sensor to be
adjusted.
5. Press ENTER key to scroll to
Offset
(see Figure
53).
6. Press UP or DOWN keys to add or subtract to the
sensor offset value.
7. Press ENTER key to save.
User
2000
Technician
1313
Engineer
9254
Use UP or DOWN keys and ENTER key to enter password
TABLE 5
LC6000/TEC-EYE Passwords (Defaults)
FIGURE 53
Adjusting Sensor Offset Value
Содержание MULTI-TEC W24AAPA
Страница 3: ...Page 3 of 88 SECTION 1 MULTI TEC LC6000 INSTALLATION INSTRUCTIONS...
Страница 36: ...Manual 2100 676B Page 36 of 88 FIGURE 25 LC6000 Wiring Diagram...
Страница 46: ...Manual 2100 676B Page 46 of 88...
Страница 47: ...Manual 2100 676B Page 47 of 88 SECTION 2 WR SERIES LC6000 INSTALLATION INSTRUCTIONS...
Страница 79: ...Manual 2100 676B Page 79 of 88 FIGURE 32 LC6000 Wiring Diagram...