Manual 2100-676B
Page
39 of 88
After each of the wall-mount units have been
addressed, had a run test performed and had the alarm
logs cleared, the rest of the system set up can proceed.
Setting Up LC6000 for Operation
The LC6000 controller will be used for the remaining
steps in the set up process.
LC6000 Status Screen
The Status screen is the default start-up screen and
also the return screen after 5 minutes of no activity on
the LC6000. The screen can be accessed any time by
pressing the ESCAPE key repeatedly.
The Status screen on the LC6000 displays the current
date, time, unit displayed, zones and unit status (see
Figure 33 on page 40).
4. Set LC Controller Date and Time
1) Press MENU key to access the Main Menu
screen.
2) Use UP or DOWN keys and ENTER key to
enter USER password 2000.
3) Press the UP or DOWN keys to scroll to the
Settings
menu; press ENTER key.
Parameter Description
Damper Time: This is the time (in seconds) allowed for
both the opening sequence and closing sequence.
Heat/Cool Time: This is the time (in seconds) allowed
for cooling sequence and heating sequence.
Status: This will display what the unit is doing as
the run test progresses. The following messages may
appear:
1. Not Active
2. Opening Damper
3. Closing Damper
4. Compressor Stage 1
5. Compressor Stage 2
6. Reheat Valve Open
7. Cooling Off
8. Electric Heat Stage 1
9. Electric Heat Stage 2
10. Heating Off
11. Run Test Stop
The unit will determine which items to test based on
the unit model number.
FIGURE 30
Clearing Unit Alarm Logs
FIGURE 29
Executing Run Test
Step Action
Time Required
A
Open economizer damper
Damper Time (150s)
B
Close economizer Damper
Damper Time (150s)
C
Turn on compressor
Heat/Cool Time (60s)
D
Enable second stage
Heat/Cool Time (60s)
E
Open reheat valve
Heat/Cool Time (60s)
F
Turn all cooling off
--
G
Turn on electric heat
Heat/Cool Time (60s)
H
Turn on electric heat stage 2
Heat/Cool Time (60s)
I
Turn off all heating
--
3. Clear Unit Alarm Logs on Each Unit
To clear the wall-mount unit alarm logs:
1) Press MENU key to go to the Main Menu
screen.
2) Use UP or DOWN keys and ENTER key to
enter TECHNICIAN password 1313.
3) Press UP or DOWN keys to scroll to
Settings
;
press ENTER key.
4) Press UP or DOWN keys to scroll to
Initialization
; press ENTER key.
5) Press UP or DOWN keys to scroll to
Initialization 1/5
; press ENTER key.
6) Press ENTER key to scroll to
Delete Alarm
Logs?
(see Figure 30).
7) Press UP or DOWN key to change
NO
to
YES
.
8) Press ENTER key to clear all alarm logs.
6) Press UP or DOWN key to change value to
ON
.
The run test will begin.
Содержание MULTI-TEC W24AAPA
Страница 3: ...Page 3 of 88 SECTION 1 MULTI TEC LC6000 INSTALLATION INSTRUCTIONS...
Страница 36: ...Manual 2100 676B Page 36 of 88 FIGURE 25 LC6000 Wiring Diagram...
Страница 46: ...Manual 2100 676B Page 46 of 88...
Страница 47: ...Manual 2100 676B Page 47 of 88 SECTION 2 WR SERIES LC6000 INSTALLATION INSTRUCTIONS...
Страница 79: ...Manual 2100 676B Page 79 of 88 FIGURE 32 LC6000 Wiring Diagram...