2. Execute a Run Test on Each Unit
Execute a run test on each unit to verify the
equipment is functioning correctly. The run test
parameters are not adjustable.
1) Press MENU key to access the Main Menu
screen.
2) Press UP or DOWN keys and ENTER key to
enter TECHNICIAN password 1313.
3) Press UP or DOWN keys to scroll to
Sys Config
;
press ENTER key.
4) Press UP key to scroll to
Run Test A10
screen.
5) Press ENTER key to scroll to
Run Test Enable
(see Figure 37).
6) Press UP or DOWN key to change value to
ON
.
The run test will begin and the screen will
change to
Run Test Summary
.
7) Press UP or DOWN key to scroll between
Run
Test Summary
(Figure 38),
Motors & Sensors
(Figure 39) and
A/C Circuit
(Figure 40)
screens.
NOTE:
If the Run Test screens have been exited out
of, they can be returned to by navigating to
Run Test A10
as provided in the instructions
above, pressing ENTER key to scroll to
Return
to Screens
, pressing UP or DOWN key to
change value to YES and pressing ENTER key.
FIGURE 37
Executing Run Test
FIGURE 38
Run Test Summary
FIGURE 39
Run Test: Motors & Sensors
FIGURE 40
Run Test: A/C Circuit
The
Run Test Summary
screen (Figure 38) contains a
readout of the test that is currently taking place, and
the Task the technician should be completing to verify
operation.
The
Motors & Sensors
screen (Figure 39) displays
output and estimated positional values for unit motors
and actuators, and also temperature and humidity
sensor values.
The
A/C Circuit
screen (Figure 40) displays all unit
inputs, outputs and calculations associated with the
A/C circuit operation.
Run Test Parameter Description
Econ Stage Time: Amount of time (in seconds)
allowed for damper blade movement in each
direction.
Cool Stage Time: Amount of time (in seconds) allowed
for each stage of cooling.
Heat Stage Time: Amount of time (in seconds)
allowed for heating stage.
3. Clear Unit Alarm Logs on Each Unit
To clear the wall-mount unit alarm logs:
1) Press MENU key to go to the Main Menu
screen.
2) Use UP or DOWN keys and ENTER key to
enter TECHNICIAN password 1313.
Содержание MULTI-TEC W24AAPA
Страница 3: ...Page 3 of 88 SECTION 1 MULTI TEC LC6000 INSTALLATION INSTRUCTIONS...
Страница 36: ...Manual 2100 676B Page 36 of 88 FIGURE 25 LC6000 Wiring Diagram...
Страница 46: ...Manual 2100 676B Page 46 of 88...
Страница 47: ...Manual 2100 676B Page 47 of 88 SECTION 2 WR SERIES LC6000 INSTALLATION INSTRUCTIONS...
Страница 79: ...Manual 2100 676B Page 79 of 88 FIGURE 32 LC6000 Wiring Diagram...