Manual 2100-676B
Page
43 of 88
2) Press UP or DOWN key until the Quick Menu in
the lower right corner of the screen displays the
Information icon ( ); press ENTER key.
3) Press UP or DOWN keys to scroll through the
Information screens until the desired unit
Information screen appears.
In addition to being able to remotely view the units,
an alarm will be generated on the LC controller for
units not communicating.
8. Clear Controller Alarm Logs
To clear the LC controller alarm logs:
1) Press MENU key to go to the Main Menu
screen.
2) Use UP or DOWN keys and ENTER key to enter
USER password 2000.
3) Press UP or DOWN keys to scroll to
Settings
;
press ENTER key.
4) Press UP or DOWN keys to scroll to
Initialization
; press ENTER key.
5) Press ENTER key to scroll to
Delete Alarm
Logs?
(see Figure 41).
6) Press UP or DOWN key to value to
YES
; press
ENTER key.
7) Press ESCAPE key several times to return to
Main Menu screen.
9. Complete Installation
Once all the installation steps have been
completed, all alarms and alarm logs have been
cleared and system verification and run test results
were satisfactory, the installation can now be
considered “complete".
Additional programming information can be found
in MULTI-TEC Service Instructions 2100-665 and
LC6000 Service Instructions 2100-669.
FIGURE 41
Clearing LC6000 Alarm Logs
Содержание MULTI-TEC W24AAPA
Страница 3: ...Page 3 of 88 SECTION 1 MULTI TEC LC6000 INSTALLATION INSTRUCTIONS...
Страница 36: ...Manual 2100 676B Page 36 of 88 FIGURE 25 LC6000 Wiring Diagram...
Страница 46: ...Manual 2100 676B Page 46 of 88...
Страница 47: ...Manual 2100 676B Page 47 of 88 SECTION 2 WR SERIES LC6000 INSTALLATION INSTRUCTIONS...
Страница 79: ...Manual 2100 676B Page 79 of 88 FIGURE 32 LC6000 Wiring Diagram...