Manual 2100-676B
Page
74 of 88
1. Using the field-provided shielded cable, make a small service loop after entering the controller and attach the provided
EMI filter at the intersection of the loop.
FIGURE 27
Communication Wiring: Termination at the Controller
2. Connect one wire to terminal #56 (negative), the other wire to terminal #57 (positive) and the drain wire to ground
terminal #60.
-
+
G
To Wall-Mount Unit 1
Control Board Terminal
Block
The steps outlined on the following pages show how to connect the communication wiring using the daisy chain
method shown in Figure 24. If using the alternate method (as shown in Figure 25), the connections to the controller
and each wall-mount unit will be the same but the filters need to be placed in the positions shown in Figure 26.
5
7
9
17
19
21
25
23
27
29
31
35
33
37
11
13
15
39
43
41
45
47
51
49
53
55
59
57
60
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
1
2
3
4
Содержание MULTI-TEC W24AAPA
Страница 3: ...Page 3 of 88 SECTION 1 MULTI TEC LC6000 INSTALLATION INSTRUCTIONS...
Страница 36: ...Manual 2100 676B Page 36 of 88 FIGURE 25 LC6000 Wiring Diagram...
Страница 46: ...Manual 2100 676B Page 46 of 88...
Страница 47: ...Manual 2100 676B Page 47 of 88 SECTION 2 WR SERIES LC6000 INSTALLATION INSTRUCTIONS...
Страница 79: ...Manual 2100 676B Page 79 of 88 FIGURE 32 LC6000 Wiring Diagram...