background image

 

 

Page 

1 of 88

Bard Manufacturing Company, Inc. 

Bryan, Ohio 43506 

www.bardhvac.com

Manual: 2100-676B
Supersedes: 2100-676A 
Date: 4-6-18

INSTALLATION INSTRUCTIONS

NOTE: LC6000 controller is required for operation when multiple MULTI-TEC 

and/or WR Series wall-mount units are used.

MULTI-TEC

®

 Wall-Mount Air Conditioner/

WR Series Wall-Mount Air Conditioner/

LC6000-100 Controller

Free Cooling Unit System

W18AAPA
W24AAPA
W24AAPB
W24AAPC
W30AAPA
W30AAPB
W30AAPC
W36AAEA
W36AAEB
W36AAEC
W36AAMA
W36AAMB
W36AAMC
W36AAPA

W36AAPB
W36AAPC
W42AAEA
W42AAEB
W42AAEC
W42AAPA
W42AAPB
W42AAPC
W48AAEA
W48AAEB
W48AAEC
W48AAEQ
W48AAMA
W48AAMB

W18LAPA
W24LAPA
W24LAPB
W30LAPA
W30LAPB
W30LAPC
W36LAPA
W36LAPB
W36LAPC
W42LAPA
W42LAPB
W42LAPC
W48LAPA
W48LAPB

W48LAPC
W48LAPQ
W60LAPA
W60LAPB
W60LAPC
W60LAPQ
W72LBPA
W72LBPB
W72LBPC
W72LBPQ

W48AAMC
W48AAPA
W48AAPB
W48AAPC
W48AAPQ
W60AAEA
W60AAEB
W60AAEC
W60AAEQ
W60AAMA
W60AAMB
W60AAMC
W60AAPA
W60AAPB

W60AAPC
W60AAPQ
W72ABEA
W72ABEB
W72ABEC
W72ABEQ
W72ABMA
W72ABMB
W72ABMC
W72ABPA
W72ABPB
W72ABPC
W72ABPQ

MULTI-TEC Wall-Mount Units

WR36APA   WR36APB   WR58APA   WR58APB

WR Series Wall-Mount Units

Содержание MULTI-TEC W24AAPA

Страница 1: ...W36AAEB W36AAEC W36AAMA W36AAMB W36AAMC W36AAPA W36AAPB W36AAPC W42AAEA W42AAEB W42AAEC W42AAPA W42AAPB W42AAPC W48AAEA W48AAEB W48AAEC W48AAEQ W48AAMA W48AAMB W18LAPA W24LAPA W24LAPB W30LAPA W30LAPB...

Страница 2: ...cond section explains the installation and set up of WR Series wall mount units with an LC6000 controller Check wall mount unit model number information found on the model serial tag prior to beginnin...

Страница 3: ...Page 3 of 88 SECTION 1 MULTI TEC LC6000 INSTALLATION INSTRUCTIONS...

Страница 4: ...mination at Additional Wall Mount Units 33 Figure 23 LC6000 Controller Circuit Install 34 Figure 24 Controller Grounding Posts 34 Figure 25 WIRING LC6000 Wiring Diagram 36 Figure 26 TEC EYE Connection...

Страница 5: ...s are designed specifically to work together The controller cannot run other brands of systems nor can other controllers run the MULTI TEC wall mount units They are a complete system and must be used...

Страница 6: ...al regulations are at a variance with instructions installer should adhere to local codes Shipping Damage Upon receipt of equipment the cartons should be checked for external signs of shipping damage...

Страница 7: ...s to be limited to the most extreme situations DANGER signs should not be used for property damage hazards unless personal injury risk appropriate to these levels is also involved WARNING Indicate s a...

Страница 8: ...cation wire 2 wire 18 gauge shielded with drain 18 gauge non shielded wire for connecting smoke detector hydrogen detector and or generator if applicable to controller CAT 6 Ethernet cable of field de...

Страница 9: ...the recirculation and obstruction of condenser discharge air does not occur Recirculation of condenser discharge air can be from either a single unit or multiple units Any object such as shrubbery a b...

Страница 10: ...for non ERV CRV Econ models 1 F G W 5 88 Electric Heat MIS 3889 Electrical Entrances Optional Supply Air Opening Side Wall Mounting Built In Shipping Location Brackets Return Air Opening Top Rain Fla...

Страница 11: ...e pre punched knockouts Two holes for the supply and return air openings must be cut through the wall as shown in Figures 4A D on pages 12 15 On wood frame walls the wall construction must be strong a...

Страница 12: ...LKING ALONG PANEL FOAM AIR SEAL DUCT RAIN FLASHING HEATER ACCESS MIS 3157 A Wall Opening and Hole Location View Right Side View RETURN AIR TOP FLASHING AT TIME OF INSTALLATION OPENING THE SIDE MOUNTIN...

Страница 13: ...AIR DUCT IS REQUIRED FROM COMBUSTABLE MATERIALS RAIN FLASHING TOP SUPPLY AIR OPENING Right Side View HEATER ACCESS TOP FLASHING AT TIME OF INSTALLATION SEAL WITH BEAD IT IS RECOMMENDED THAT A BEAD OF...

Страница 14: ...3 4 32 12 5 1 2 2 NOTES WALL STRUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SIDE MOUN...

Страница 15: ...M COMBUSTIBLE MATERIALS REQUIRED DIMENSIONS TO MAINTAIN OPENING COMBUSTIBLE MATERIALS B D E PANEL AIR DUCT IS REQUIRED 32 10 1 2 Right Side View SUPPLY AIR RECOMMENDED 1 CLEARANCE FROM MIS 3789 RAIN F...

Страница 16: ...WALL INSTALLATION OPENING WALL BEFORE MOUNT ON UNIT OPENING BEFORE INSTALLATION BOTTOM MOUNTING CONCRETE BLOCK WALL INSTALLATION BRACKET MOUNT ON OPENING WOOD OR STEEL SIDING OPENING INSTALLING UNIT...

Страница 17: ...AL DIMENSIONS 2 x 4 S 2 x 6 S OR STRUCTURAL STEEL ATTACH TO TOP 1 000 CLEARANCE 1 000 CLEARANCE PLATE OF WALL C SEE UNIT DIMENSIONS FIGURE 1 2 OPENING RETURN DUCT 2 x 6 ATTACH TO BOTTOM OVER FRAME PLA...

Страница 18: ...OUTSIDE FALSE WALL INSTALLATION CEILING RAIN FLASHING RAIN FLASHING SUPPLY DUCT MAY BE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN FINISHEDCEILING WALL CLOSETWALL SURFACE SLEEVE SUPPLY DUCT...

Страница 19: ...the tab located in the bottom left hand corner of the disconnect opening under the disconnect access panel straight out This tab will now line up with the slot in the door When shut a padlock may be p...

Страница 20: ...5 A10 A15 A20 230 208 1 1 1 1 1 or 2 1 or 2 32 32 58 84 110 50 50 60 90 125 8 8 6 4 2 10 10 10 8 6 58 58 26 52 60 60 30 60 6 6 10 6 10 10 10 10 W42AAPB00 B0Z B06 B09 B15 B18 230 208 3 1 1 1 1 1 25 25...

Страница 21: ...1 1 1 1 1 1 or 2 26 32 47 58 84 35 35 50 60 90 8 8 8 6 4 10 10 10 10 8 58 26 60 30 6 10 10 10 W30LAPB00 B0Z B09 B15 230 208 3 1 1 1 19 33 51 20 35 60 12 8 6 12 10 10 W30LAPC00 C0Z C09 C15 460 3 1 1 1...

Страница 22: ...0 208 1 1 or 3 134 140 1 0 6 58 52 26 60 60 30 6 6 10 10 10 10 W72ABEB15 230 208 3 1 or 2 83 90 4 8 38 52 40 60 8 6 10 10 W72ABEC15 460 3 1 40 45 8 10 These Minimum Circuit Ampacity values are to be u...

Страница 23: ...oling and heating setpoints in stand alone mode 1 Connect the TEC EYE diagnostic tool to the control board located in the unit 2 From the Status screen press UP or DOWN key until Quick Menu displays S...

Страница 24: ...ALLATION FIGURE 12 Typical LC6000 Component Location Transformer RJ11 Cable to Display Four Fused Power Supply Terminals Terminal Block Smoke Alarm Jumper Hydrogen Alarm Jumper Generator Run Alarm Jum...

Страница 25: ...rical shock hazard Disconnect VAC power supplies before servicing Failure to do so could result in electric shock or death WARNING IMPORTANT When working with circuit board components Bard recommends...

Страница 26: ...emperature Humidity Sensor Installation 1 Connect wires from the 18 gauge shielded cable to terminals 12 13 18 19 and 22 2 Connect the other end of the shielded cable to the sensor terminals Be sure w...

Страница 27: ...he two wire connections for the optional remote temperature sensor are not polarity sensitive TB Wire Mark Description 20 B7 Indoor Remote Sensor Zone 1 optional 21 GND Ground Zone 3 Optional Remote T...

Страница 28: ...pers across terminals 6 and 7 smoke detector 8 and 9 hydrogen detector and 10 and 11 generator run Remove the factory installed jumpers before connecting to the detectors and or generator FIGURE 16 LC...

Страница 29: ...ing in same conduit as supply wiring Route communication wiring and power supply wiring in their own separate conduits LC6000 Controller Wall Mount Unit Wall Mount Unit FIGURE 17 Communication Wiring...

Страница 30: ...t 1 Unit 2 up to 14 units Unit 3 Unit 4 Unit 5 Place filter here end unit Daisy Chain Wiring Alternate Wiring Place filter here end unit NOTE Line filters can be on either the unit or controller which...

Страница 31: ...al 57 positive and the drain wire to ground terminal 60 G To Wall Mount Unit 1 Control Board RS485 The steps outlined on the following pages show how to connect the communication wiring using the dais...

Страница 32: ...terminal block Make sure to match and symbols on controller terminal blocks 2 Connect the wires matching the terminal designations of the controller terminals Leave the drain wire loose 3 Connect anot...

Страница 33: ...RS485 PLAN RS485 R T R T RS485 R T R T 2 Connect the wires matching the terminal designations of the controller terminals Cap the loose drain with a wire nut or electrical tape From Wall Mount Unit 1...

Страница 34: ...ing lug must be field supplied Install as shown in Figure 24 Failing to ground the controller box properly could result in damage to the equipment FIGURE 24 Controller Grounding Posts A reliable earth...

Страница 35: ...3 VDC Power for B3 Z2 Humidity 24 VDC Power for B4 Z3 Humidity 25 VDC Power for B10 Pressure 26 B8 Indoor Remote Temperature Sensor Zone 2 27 GND Ground 28 B9 Indoor Remote Temperature Sensor Zone 3 2...

Страница 36: ...Manual 2100 676B Page 36 of 88 FIGURE 25 LC6000 Wiring Diagram...

Страница 37: ...he MULTI TEC wall mount air conditioners allows for complete control and monitoring through the use of the provided TEC EYE hand held monitor The menu driven interface provides users the ability to sc...

Страница 38: ...parameter see Figure 29 TEC EYE Status Screen The Status screen is the default start up screen and also the return screen after 5 minutes of no activity The screen can be accessed any time by pressin...

Страница 39: ...llowing messages may appear 1 Not Active 2 Opening Damper 3 Closing Damper 4 Compressor Stage 1 5 Compressor Stage 2 6 Reheat Valve Open 7 Cooling Off 8 Electric Heat Stage 1 9 Electric Heat Stage 2 1...

Страница 40: ...ed or alternatively temperature only sensors may be purchased instead The LC is capable of utilizing four temperature sensors and three humidity sensors The system will need to be configured for the v...

Страница 41: ...enu screen 2 Use UP or DOWN keys and ENTER key to enter USER password 2000 To enable disable Zone 1 Remote Temperature 1 Press MENU key to go to the Main Menu screen 2 Use UP or DOWN keys and ENTER ke...

Страница 42: ...ble sensor or change value to OFF to disable sensor FIGURE 38 Enable Disable Zone 2 Remote Temperature Sensor FIGURE 39 Enable Disable Zone 3 Remote Temperature Sensor 6 Enter Total Number of Units 1...

Страница 43: ...NTER key to enter USER password 2000 3 Press UP or DOWN keys to scroll to Settings press ENTER key 4 Press UP or DOWN keys to scroll to Initialization press ENTER key 5 Press ENTER key to scroll to De...

Страница 44: ...echnician 1313 Initialization Clear Logs User 2000 System Default Engineer 9254 Restart User 2000 ADDITIONAL INFORMATION Parameter Config Engineer 9254 Alarm Export User 2000 G Logout Used to log out...

Страница 45: ...n Off by BMS Unit Off by BMS Off by LC Unit Off by LC Master Off by Keypad Unit Off by Keypad Emergency Vent Emergency Vent Mode Active Emergency Cool Emergency Cool Mode Active Emergency Off Emergenc...

Страница 46: ...Manual 2100 676B Page 46 of 88...

Страница 47: ...Manual 2100 676B Page 47 of 88 SECTION 2 WR SERIES LC6000 INSTALLATION INSTRUCTIONS...

Страница 48: ...ss Panel to Allow Access to Control Panel 57 Figure 5 Fold Out Diverter 58 Figure 6 Downward Curved Diverter Blades 58 Figure 7 View of Installed Grille 58 Figure 8 Mounting Instructions 59 Figure 9 E...

Страница 49: ...e Required for Service Access and Adequate Condenser Airflow 54 Table 2 Minimum Clearance Required to Combustible Materials 54 Table 3 Electrical Specifications 62 Table 4 LC6000 100 Terminal Block In...

Страница 50: ...wall sleeve may be necessary between the supply and return flanges and grilles These instructions explain the recommended method to install the air cooled self contained unit and the electrical wirin...

Страница 51: ...publishers Air Conditioning Contractors of America ACCA 1712 New Hampshire Ave N W Washington DC 20009 Telephone 202 483 9370 Fax 202 234 4721 American National Standards Institute ANSI 11 West Street...

Страница 52: ...t with the necessary capacity and rigging to safely move install the systems Water to prime drain traps Electrical supplies Various size circuit breakers for the shelter AC breaker box see Table 3 on...

Страница 53: ...LS OPTIONS X Standard accessories including airflow sensor dirty filter sensor pressure transducers crankcase heater S All standard accessories plus additional Bard GuardTM security features and secur...

Страница 54: ...condenser fan condenser coil and filter drier The design allows for installations to place units within close proximity without complicating maintenance and repair To maintain full serviceability side...

Страница 55: ...00 31 13 34 13 3 50 43 00 2 69 17 00 3 88 All dimensions are in inches Dimensional drawings are not to scale 2 Pitch Rain Hood Access Panel Condenser Built In Service Port Cover K N D 7 125 I 1 500 C...

Страница 56: ...ay be best to spot some electrical knockouts such as those located on the sides of the wall mount unit before units are mounted and access is unavailable or limited see Figure 2 to locate pre punched...

Страница 57: ...ater into evaporator drain pan directly above left and right drain fittings until coiled drain tubes in blower section are visibly full Evaporator Drain Pan Left Side Drain Hose Evaporator Drain Pan R...

Страница 58: ...g drawn back into the return air opening With the optimized air pattern the shelter should experience distributed air at the opposite end of the room To accomplish this the grille has two special feat...

Страница 59: ...RED DIMENSIONS TO MAINTAIN 1 MIN CLEARANCE FROM COMBUSTIBLE MATERIALS 32 12 5 1 2 2 29 Top Of Unit Foam Air Seal To Support Rain Flashing Entire Length Of Top Of Calking Along Wall Structure Seal With...

Страница 60: ...l Wall Frame Inside Sheeting Typical Building Outside Sheeting MIS 3897 SUPPLY GRILLE MOUNT ON UNIT RETURN AIR OPENING RETURN AIR OPENING SUPPLY AIR OPENING SUPPLY AIR OPENING CONCRETE BLOCK WALL INST...

Страница 61: ...AME EXTERIOR FINISH WALL OVER FRAME ATTACH TO BOTTOM PLATE OF WALL 1 000 CLEARANCE ALL AROUND DUCT ATTACH TO TOP PLATE OF WALL OPENING MIS 3895 THIS STRUCTURAL MEMBER LOCATED TO MATCH STUD SPACING FOR...

Страница 62: ...guide it is important to electrically connect properly sized fuses and conductor wires in accordance with the National Electrical Code and all local codes Model Rated Volts Phase No Field Power Circu...

Страница 63: ...OLTAGE COMMUNICATION WIRE ENTRANCE HIGH VOLTAGE POWER WIRE ENTRANCE MIS 3927 FIGURE 15 Side Communication and Power Wire Entrances Recommended FIGURE 14 VAC Supply Wiring Landing Points Route wires in...

Страница 64: ...ptional Unit Control Voltage Wiring 230 208V 1 phase and 3 phase equipment use dual primary voltage transformers All equipment leaves the factory wired on 240V tap It is very important that the correc...

Страница 65: ...table operating voltage range for the 240 and 208V taps are 240V Tap 253 216 and 208 Tap 220 197 do not adjust transformer 2 If incoming AC voltage is 220VAC or above shut off AC breaker to unit and m...

Страница 66: ...until value displays correctly 5 Press ENTER key to save and scroll to next parameter 6 Press ESCAPE key until Main Menu screen is displayed During installation the ability to run in stand alone mode...

Страница 67: ...ALLATION FIGURE 19 Typical LC6000 Component Location Transformer RJ11 Cable to Display Four Fused Power Supply Terminals Terminal Block Smoke Alarm Jumper Hydrogen Alarm Jumper Generator Run Alarm Jum...

Страница 68: ...rical shock hazard Disconnect VAC power supplies before servicing Failure to do so could result in electric shock or death WARNING IMPORTANT When working with circuit board components Bard recommends...

Страница 69: ...Temperature Humidity Sensor Installation 1 Connect wires from the 18 gauge shielded cable to terminals 12 13 18 19 and 22 2 Connect the other end of the shielded cable to the sensor terminals Be sure...

Страница 70: ...he two wire connections for the optional remote temperature sensor are not polarity sensitive TB Wire Mark Description 20 B7 Indoor Remote Sensor Zone 1 optional 21 GND Ground Zone 3 Optional Remote T...

Страница 71: ...umpers across terminals 6 and 7 smoke detector 8 and 9 hydrogen detector and 10 and 11 generator run Remove the factory installed jumpers before connecting to the detectors and or generator FIGURE 23...

Страница 72: ...ication purposes only Do not run communication wiring in same conduit as supply wiring Route communication wiring and power supply wiring in their own separate conduits FIGURE 25 Communication Wiring...

Страница 73: ...4 Place filter here Unit 1 Unit 2 Unit 3 Unit 4 Place filter here Place filter here NOTE Line filters can be on either the unit or controller whichever device is on the end of the chain No matter how...

Страница 74: ...57 positive and the drain wire to ground terminal 60 G To Wall Mount Unit 1 Control Board Terminal Block The steps outlined on the following pages show how to connect the communication wiring using th...

Страница 75: ...symbols on controller terminal block 2 Connect the wires matching the terminal designations of the controller terminals Leave the drain wire loose 3 Connect another cable in a similar fashion daisy ch...

Страница 76: ...esignations of the controller terminals Cap the loose drain with a wire nut or electrical tape 3 Continue daisy chaining units by connecting to to and wire nutting drain together until last unit which...

Страница 77: ...ding lug must be field supplied Install as shown in Figure 31 Failing to ground the controller box properly could result in damage to the equipment FIGURE 31 Controller Grounding Posts A reliable eart...

Страница 78: ...3 VDC Power for B3 Z2 Humidity 24 VDC Power for B4 Z3 Humidity 25 VDC Power for B10 Pressure 26 B8 Indoor Remote Temperature Sensor Zone 2 27 GND Ground 28 B9 Indoor Remote Temperature Sensor Zone 3 2...

Страница 79: ...Manual 2100 676B Page 79 of 88 FIGURE 32 LC6000 Wiring Diagram...

Страница 80: ...5 minutes of no activity The screen can be accessed any time by pressing the ESCAPE key repeatedly SYSTEM SET UP FIGURE 33 TEC EYE Connection to Unit Control Modular Phone Connector for TEC EYE Hand...

Страница 81: ...N key to navigate to Economizer Setup A2 screen 10 Press ENTER key to scroll to Type see Figure 36 11 Press UP or DOWN keys to change economizer type to None Drybulb Temperature and Humidity or Enthal...

Страница 82: ...eens pressing UP or DOWN key to change value to YES and pressing ENTER key FIGURE 37 Executing Run Test FIGURE 38 Run Test Summary FIGURE 39 Run Test Motors Sensors FIGURE 40 Run Test A C Circuit The...

Страница 83: ...oceed FIGURE 41 Clearing Unit Alarm Logs The Status screen on the LC6000 displays the current date time unit displayed zones and unit status see Figure 43 4 Set LC Controller Date and Time 1 Press MEN...

Страница 84: ...ature and humidity sensors installed The system is shipped with one combination temperature and humidity sensor Additional combination sensors may be purchased or alternatively temperature only sensor...

Страница 85: ...or FIGURE 48 Enable Disable Zone 1 Remote Temperature Sensor To enable disable Zone 2 Remote Temperature 1 Press MENU key to go to the Main Menu screen 2 Use UP or DOWN keys and ENTER key to enter USE...

Страница 86: ...wer right corner of the screen displays the Information icon press ENTER key 3 Press UP or DOWN keys to scroll through the Information screens until the desired unit Information screen appears In addi...

Страница 87: ...tart User 2000 Parameter Config Engineer 9254 Alarm Export User 2000 Logout Used to log out of the current password level Entering back into the menu requires password ADDITIONAL INFORMATION Setpoints...

Страница 88: ...or cooling calls are present Power Loss Unit has experienced a loss of main utility power Alarm only available with inverter units Freecooling Unit is actively economizing Optimized Cool Unit is mecha...