B-2 Parameter Values
MN715J
Parameter Values
Level 1 Continued
INPUT Block
Parameter
Adjustable Range
Factory
Setting
User
Setting
OPERATING MODE
Keypad
Standard Run
7 Speed
Fan Pump 2Wire
Fan Pump 3Wire
Process Control
3SPD ANA 2WIRE
3SPD ANA 3WIRE
EPOT 2WIRE
EPOT 3 WIRE
Keypad
ANA CMD SELECT
Potentiometer
0-10 Volts
0-5 Volts
4 TO 20 mA
0 TO 20 mA
None
Potentio-
meter
ANA CMD INVERSE
OFF, ON
OFF
ANA CMD OFFSET
-20.0 to +20.0%
0.0%
ANA CMD GAIN
80.0% to 120%
100.0%
ANA CMD FILTER
0-6
1
OUTPUT Block
Parameter
Adjustable Range
Factory
Setting
User
Setting
RELAY OUTPUT
Ready
Zero Speed
At Speed Band
At Set Speed
Overload
Underload
Keypad Control
Fault
Drive On
Reverse
Process Error
Ready
ZERO SPD SET PT
0-Max Output Freq
6.00Hz
AT SPEED BAND
0-20.00Hz
20.00Hz
SET SPEED POINT
0-Max Output Freq
60.00Hz
OVERLOAD SET PT
0-PK Current Limit
Factory Set
UNDERLOAD SET PT
0-PK Current Limit
Factory Set
ANALOG OUT TYPE
0-10 VOLTS, 0-5 VOLTS,
4TO20mA, 0TO20mA
0-10 VOLTS
Содержание ID15J1F50-ER
Страница 1: ...Series 15J Inverter Control 7 04 MN715J Installation and Operating Manual...
Страница 5: ...iv Table of Contents MN715J...
Страница 11: ...2 4 General Information MN715J...
Страница 59: ...4 22 Programming and Operation MN715J...
Страница 75: ...6 6 Specifications and Product Data MN715J...
Страница 79: ...A 4 Dynamic Brake Hardware MN715J...
Страница 86: ...Appendix C Remote Keypad Mounting Template MN715J Remote Keypad Mounting Template C 1...