MN715J
Receiving and Installation 3-17
Standard Run 3 Wire Connection
Figure 3-11 Standard Run 3-Wire Connection Diagram
11
12
13
14
15
16
17
18
Forward
Reverse
Stop
Accel/Decel Select
Speed Select 1
Speed Select 2
External Trip
Input Common
Refer to Figure 3Ć9.
J4
Refer to Table 3Ć7
See recommended terminal
tightening torques in Section 6.
Table 3-7 Speed Select
Function
Speed Select 1
Speed Select 2
ANA CMD Select
Open
Open
Preset Speed 1
Closed
Open
Preset Speed 2
Closed
Closed
Preset Speed 3
Open
Closed
J4-11
Momentary CLOSED starts Forward motor rotation.
J4-12
Momentary CLOSED starts Reverse motor rotation.
J4-13
Momentary OPEN motor decels to stop (depending on Keypad Stop mode).
J4-14
OPEN selects ACC / DEC / S-CURVE group 1.
CLOSED selects group 2.
J4-15
Selects preset speeds as defined in Table 3-7.
J4-16
Selects preset speeds as defined in Table 3-7.
J4-17
If J4-17 is connected, you must set Level 2 Protection block, External Trip to
“ON” to activate the opto input.
OPEN causes an external trip fault. The control will disable and the motor
coasts to a stop. An external trip fault is displayed (also logged in the fault log).
CLOSED allows normal operation.
Содержание ID15J1F50-ER
Страница 1: ...Series 15J Inverter Control 7 04 MN715J Installation and Operating Manual...
Страница 5: ...iv Table of Contents MN715J...
Страница 11: ...2 4 General Information MN715J...
Страница 59: ...4 22 Programming and Operation MN715J...
Страница 75: ...6 6 Specifications and Product Data MN715J...
Страница 79: ...A 4 Dynamic Brake Hardware MN715J...
Страница 86: ...Appendix C Remote Keypad Mounting Template MN715J Remote Keypad Mounting Template C 1...