Receiving and Installation 3-5
Figure 3-1 Recommended System Grounding
L1
AC Main Supply
Safety Ground
Driven
earth ground
rod
(plant ground)
Four Wire “W
ye”
L1
L2
L3
Earth
L2
L3
T1
T3
Line Reactor
Load Reactor
Route all 4 wires L1, L2, L3 and
Earth
(ground)
together in conduit or cable.
Route
all 4 wires T1, T2, T3 and motor ground
together
in conduit or shielded cable.
Connect
all wires (including
motor
ground) inside the
motor
terminal box.
Ground per NEC and Local codes.
Note:
A line reactor is recommended and must be ordered separately
.
Note:
A load reactor is recommended and must be ordered separately
.
Baldor Control
T2
Note:
Use
shielded cable for control
signal
wires. Route control
signal
wires in conduit. These
wires
must be kept separate
from
power and motor wires.