3-20 Receiving and Installation
MN715J
Fan Pump 3 Wire Connection
Figure 3-14 Fan/Pump 3 Wire Connection Diagram
11
12
13
14
15
16
17
18
Forward
Reverse
Stop
Firestat
Freezestat
Run Command
Speed Command
Input Common
J4
Refer to Table 3Ć10
See recommended terminal
tightening torques in Section 6.
Table 3-10
Function
Firestat
Freezestat Comment
ANA CMD Select
Closed
Closed
Firestat and Freezestat are alarm
i
t th t
id ll
d
Preset
Speed 1
Open
Closed
inputs that override all speed
commands including the keypad
Preset
Speed 1
Open
Open
commands including the keypad.
Preset
Speed 2
Closed
Open
J4-11
Momentary CLOSED starts Forward motor rotation.
J4-12
Momentary CLOSED starts Reverse motor rotation.
J4-13
Momentary OPEN motor decels to stop (depending on Keypad Stop mode).
J4-14
OPEN selects preset speed #1 regardless of the Speed Command input J4-13.
CLOSED allows normal operation.
J4-15
OPEN selects preset speed #2 regardless of the Speed Command input J4-13.
CLOSED allows normal operation.
J4-16
OPEN selects direction commands from Keypad.
CLOSED selects direction commands from terminal strip.
J4-17
OPEN selects speed commanded from Keypad.
CLOSED selects terminal strip speed source (selected in the Level 1 Input block,
ANA CMD Select parameter).
Содержание ID15J1F50-ER
Страница 1: ...Series 15J Inverter Control 7 04 MN715J Installation and Operating Manual...
Страница 5: ...iv Table of Contents MN715J...
Страница 11: ...2 4 General Information MN715J...
Страница 59: ...4 22 Programming and Operation MN715J...
Страница 75: ...6 6 Specifications and Product Data MN715J...
Страница 79: ...A 4 Dynamic Brake Hardware MN715J...
Страница 86: ...Appendix C Remote Keypad Mounting Template MN715J Remote Keypad Mounting Template C 1...