3-16 Receiving and Installation
MN715J
Keypad Connection
The Keypad operating mode allows the control to be operated from the
keypad. In this mode, no control connection wiring is required. However, the
Stop, Accel/Decel select and External Trip inputs may optionally be used. All
other digital inputs are inactive. The analog output and relay outputs remain
active at all times.
For operation in Keypad mode, set the Level 1 Input block, Operating Mode
parameter to Keypad.
To use the Stop input, J4-13 must be connected and the Level 1 Keypad
Setup block, LOC. Hot Start parameter must be set to ON. The Stop line is
normally closed. When opened, the motor will COAST or REGEN to a stop
depending upon the setting of Level 1 Keypad Setup block Keypad Stop Key
parameter value. Closing the input will immediately start the motor if a run
command was given before the stop line was opened.
The Accel/Decel select input is used to select ACC / DEC / S-CURVE group 1
or group 2. This connection is made at J4-14.
The External Trip input is used to cause a fault condition during a motor
over-temperature condition. The External Trip input (J4-17) must be
connected and the External Trip parameter in the Level 2 Protection block
must be set to ON. When J4-17 is opened, the motor will coast to a stop and
an External Trip fault will be displayed on the keypad display.
Figure 3-10 Keypad Connection Diagram
11
12
13
14
15
16
17
18
Accel/Decel Select
External Trip
J4
Input Common
Refer to Figure 3Ć9.
See recommended terminal
tightening torques in Section 6.
Stop
Keypad Only Connection
J4-13
If J4-13 is connected, you must set Level 1 Keypad Setup block, LOC. Hot Start
parameter to “ON” to activate the opto input.
CLOSED allows normal control operation.
OPEN disables the control and the motor will coast or brake to a stop. The motor
will restart when J4-13 closes after open.
J4-14
OPEN selects ACC / DEC / S-CURVE group 1.
CLOSED selects group 2.
J4-17
If J4-17 is connected, you must set Level 2 Protection block, External Trip to
“ON” to activate the opto input.
OPEN causes an external trip fault. The control will disable and the motor
coasts to a stop. An external trip fault is displayed (also logged in the fault log).
CLOSED allows normal operation.
Содержание ID15J1F50-ER
Страница 1: ...Series 15J Inverter Control 7 04 MN715J Installation and Operating Manual...
Страница 5: ...iv Table of Contents MN715J...
Страница 11: ...2 4 General Information MN715J...
Страница 59: ...4 22 Programming and Operation MN715J...
Страница 75: ...6 6 Specifications and Product Data MN715J...
Страница 79: ...A 4 Dynamic Brake Hardware MN715J...
Страница 86: ...Appendix C Remote Keypad Mounting Template MN715J Remote Keypad Mounting Template C 1...