MN715J
Programming and Operation 4-15
Parameter Block Definitions
Level 1 Continued
OUTPUT
Continued
Fault
Active when a fault condition is present.
Drive On
Active when control is “Ready” and is being commanded to operate the
motor.
Reverse
Active when control is operating in the reverse direction.
Process Error
Active when the PID control loop process is outside the range
specified by the Level 2 Process Control block, AT Setpoint band parameter.
Zero SPD Set PT
The output frequency at which the zero speed relay output becomes
active (turns on). When the output frequency is less than the Zero SPD Set PT, the
relay output becomes active. This is useful in applications where a motor brake will be
interlocked into the operation of the motor control.
At Speed Band
A frequency band within which the at speed relay output becomes
active (turns on). For example, if the at speed band is set to
±
5Hz the relay output
becomes active when the output frequency to the motor is within 5Hz of the
commanded motor frequency. This is useful when another machine must not start (or
stop) until the motor reaches operating speed.
Set Speed Point
The frequency at which the at set speed relay output becomes active
(turns on). When the frequency is greater than the set speed point parameter, the
relay output becomes active. This is useful when another machine must not start (or
stop) until the motor exceeds a predetermined speed.
Overload Set Point
When the output current exceeds this value, the overload output is
turned on.
Underload Set Point
When the output current is less than this value, the underload
output is turned on.
Analog OUT Type
0-10VDC, 0-5VDC, 4-20mA or 0-20mA.
Analog Output
Analog output that may be configured to represent one of the
following conditions:
Frequency
Represents the output frequency; where max output = MAX Hz (slip
freq. compensation is not included).
Freq Command
Represents the commanded frequency where max output =
MAX Hz.
AC Current
Represents the value of the output current where max output = Full
load current (A
RMS
).
AC Voltage
Represents the value of the output voltage where max output =
Control Input Voltage.
Bus Voltage
Represents motor power where half max output = 325VDC for
230VAC input (650VDC for 460VAC input).
Control Temp
Represents the heat sink temperature of the control where max
output = maximum heat sink temperature.
Process Feedback
Represents the process feedback signal where max output =
100% feedback signal.
Set Point Command
Represents the setpoint command value where max output
= 100% commanded value.
Zero Cal
Output is minimum used to calibrate an external meter.
100% Cal
Output is maximum used to calibrate an external meter.
Analog Scale
Scale factor for the Analog Output voltage.
Useful to set the full scale range for external meters.
Содержание ID15J1F50-ER
Страница 1: ...Series 15J Inverter Control 7 04 MN715J Installation and Operating Manual...
Страница 5: ...iv Table of Contents MN715J...
Страница 11: ...2 4 General Information MN715J...
Страница 59: ...4 22 Programming and Operation MN715J...
Страница 75: ...6 6 Specifications and Product Data MN715J...
Страница 79: ...A 4 Dynamic Brake Hardware MN715J...
Страница 86: ...Appendix C Remote Keypad Mounting Template MN715J Remote Keypad Mounting Template C 1...