NO
ERROR
MESSAGE
DEFINITIONS
ERROR REASONS
15
SUPPLY ERROR
Fault in 3 Phase line
inputs.
Check 3 Phase line inputs.
16
CONTACTOR
ERROR
MCF input is not
activated during [T01]
period.
a) Check auxiliary contact connections of motor
contactors (K1-K2).
b) Check connection of programmable input which
defined as MCF.
17
BRAKE ERROR
BRF input is not
activated during [T02]
period.
a) Be sure that brake contactor is (KF) working
properly.
b) Be sure that mechanical brake is working properly.
c) Check connection and functionality of mechanical
brake switches.
d) Check connection of programmable input which
defined as BRF.
18
PARAMETER
LOSS
(Permanent
Error)
Device parameters are
different from the saved
one.
a) Enter 834 code in “SERVICES” menu to delete
permanent error.
b) Check all parameters.
F/7.5.5.02.95 R:1
45