Installation,
Wiring,
and
Specifications
2--40
Installation, Wiring, and Specifications
DL105 PLC User Manual, 3rd Edition
sensors in the input circuit. Note that on the F1--130DA, the +24V output cannot
power its output circuits, because they require AC voltages.
External Power Requirements
100 -- 240 +10% --15%
Communication Port
K--Sequence, 9600 baud, 8 data bits, odd parity
Programming cable type
D2--DSCBL
Internal Field Supply Ratings
+24VDC , 0.5A maximum, isolated
Operating Temperature
32 to 140
F (0 to 60
_
C)
Storage Temperature
--4 to 158
F (--20 to 70
_
C)
Relative Humidity
5 to 95% (non-condensing)
Environmental air
No corrosive gases permitted
Vibration
MIL STD 810C 514.2
Shock
MIL STD 810C 516.2
Noise Immunity
NEMA ICS3--304
Terminal Type
Removable
Wire Gauge
One AWG14 or two AWG16, AWG24 minimum
Parameter
High--Speed Inputs, X0 -- X3
Standard DC Inputs X4 -- X11
Input Voltage Range
10 -- 26.4 VDC
10 -- 26.4 VDC or 21.6 -- 26.4 VAC
Maximum Voltage
30 VDC (5 kHz maximum frequency)
30 VDC
Minimum Pulse Width
100
μ
S
N/A
ON Voltage Level
> 9.0 VDC
> 9.0 VDC
OFF Voltage Level
< 2.0 VDC
< 2.0 VDC
Input Impedance
2.8 k
Ω
@ 12 -- 24 VDC
2.8 k
Ω
@ 12 -- 24 VDC
Minimum ON Current
>3 mA
>3 mA
Maximum OFF Current
< 0.5 mA
<0.5 mA
OFF to ON Response
<50
μ
S
2 -- 8 mS, 4 mS typical
ON to OFF Response
< 50
μ
S
2 -- 8 mS, 4 mS typical
Status Indicators
Logic side
Logic side
Commons
4 channels / common x 1 bank
4 channels / common x 1 bank,
2 channels / common x 1 bank
Operating Voltage
20 -- 140 VAC, 47 -- 63 Hz
Peak Voltage
400 VAC
On Voltage Drop
1.3 VAC @ 2 A
Max Current
1.7 A / point, subject to derating
Max leakage current
1 mA @ 400 VAC
Max inrush current
30 A for 10 mS, 15 A for 100 mS
Minimum Load
10 mA
OFF to ON Response
8.33 mS @ 60 Hz, zero-crossing,
10 mS @ 50 Hz, zero-crossing
ON to OFF Response
8.33 mS @ 60 Hz, zero-crossing,
10 mS @ 50 Hz, zero-crossing
Status Indicators
Logic Side
Commons
2 channels / common x 4 banks
Fuses
None (external recommended)
F1--130DA
General
Specifications
DC Input
Specifications
AC Output
Specifications
Содержание DL105
Страница 2: ...DL105 PLC User Manual Manual Number D1 USER M...
Страница 308: ...1B DL105 Error Codes In This Appendix Error Code Table...
Страница 314: ...1C Instruction Execution Times In This Appendix Introduction Instruction Execution Times...
Страница 324: ...1D Special Relays In This Appendix DL105 PLC Special Relays...
Страница 327: ...1E PLC Memory In This Appendix DL105 PLC Memory...
Страница 329: ...1F European Union Directives CE In This Appendix European Union EU Directives Basic EMC Installation Guidelines...