Standard
RLL
Instructions
5--32
Standard RLL Instructions
Timer, Counter, and Shift Register Instructions
DL105 PLC User Manual, 3rd Edition
Counters are used to count events . The counters available are up counters,
up/down counters, and stage counters (used with RLL
PLUS
programming).
The up counter has two inputs, a count input and a reset input. The maximum count
value is 9999. The timing diagram below shows the relationship between the counter
input, counter reset, associated discrete bit, current value, and counter preset.
X1
X1
CT1
1
2
3
4
0
Current
Value
CNT
CT1
K3
X2
X2
Counter preset
Up
Reset
Counts
The up down counter has three inputs, a count up input, count down input and reset
input. The maximum count value is 99999999. The timing diagram below shows the
relationship between the counter input, counter reset, associated discrete bit,
current value, and counter preset.
X1
X1
CT2
1
2
1
2
3
0
Current
Value
X2
X2
UDC
CT2
K3
X3
X3
Counter preset
Up
Down
Reset
Counts
The stage counter has a count input and is reset by the RST instruction. This
instruction is useful when programming using the RLL
PLUS
structured programming.
The maximum count value is 9999. The timing diagram below shows the relationship
between the counter input, associated discrete bit, current value, counter preset and
reset instruction.
X1
X1
CT2
1
2
3
4
0
Current
Value
SGCNT
CT2
K3
RST
CT2
Counter preset
Up
Counts
Using Counters
Содержание DL105
Страница 2: ...DL105 PLC User Manual Manual Number D1 USER M...
Страница 308: ...1B DL105 Error Codes In This Appendix Error Code Table...
Страница 314: ...1C Instruction Execution Times In This Appendix Introduction Instruction Execution Times...
Страница 324: ...1D Special Relays In This Appendix DL105 PLC Special Relays...
Страница 327: ...1E PLC Memory In This Appendix DL105 PLC Memory...
Страница 329: ...1F European Union Directives CE In This Appendix European Union EU Directives Basic EMC Installation Guidelines...