Appendix
F
EU
Directives
F--6
European Union Directives
DL105 PLC User Manual, 3rd Edition
A heavy-duty star earth terminal block should be provided in every cubicle for the
connection of all earth ground straps, protective earth ground connections, mains
filter earth ground wires, and mechanical assembly earth ground connections. This
should be installed to comply with safety and EMC requirements, local standards, and
the requirements found in IEC 1000--5--2.The Machinery Directive also requires that
the common terminals of PLC input modules, and common supply side of loads driven
from PLC output modules should be connected to the protective earth ground
terminal.
Key
Serial Communication Cable
Equi-potential Bond
Adequate site earth grounding must be provided for equipment containing modern
electronic circuitry. The use of isolated earth electrodes for electronic systems is
forbidden in some countries. Make sure you check any requirements for your
particular destination. IEC 1000--5--2 covers equi-potential bonding of earth grids
adequately, but special attention should be given to apparatus and control cubicles
that contain I/O devices, remote I/O racks, or have inter-system communications with
the primary PLC system enclosure. An equi-potential bond wire must be provided
alongside all serial communications cables, and to any separate items of the plant
which contain I/O devices connected to the PLC. The diagram shows an example
of four physical locations connected by a communications cable.
Good quality 24 AWG minimum twisted-pair shielded cables, with overall foil and
braid shields are recommended for analog cabling and communications cabling
outside of the PLC enclosure. To date it has been a common practice to only provide
an earth ground for one end of the cable shield in order to minimize the risk of noise
caused by earth ground loop currents between apparatus. The procedure of only
grounding one end, which primarily originated as a result of trying to reduce hum in
audio systems, is no longer applicable to the complex industrial environment.
Shielded cables are also efficient emitters of RF noise from the PLC system, and can
interact in a parasitic manner in networks and between multiple sources of
interference.
Screened
Cable
Equi-potential
Bond
Control Cubicle
To Earth
Block
Conductive
Adapter
Serial
I/O
Internal Enclosure
Grounding
Equi--potential
Grounding
Communications
and Shielded
Cables
Содержание DL105
Страница 2: ...DL105 PLC User Manual Manual Number D1 USER M...
Страница 308: ...1B DL105 Error Codes In This Appendix Error Code Table...
Страница 314: ...1C Instruction Execution Times In This Appendix Introduction Instruction Execution Times...
Страница 324: ...1D Special Relays In This Appendix DL105 PLC Special Relays...
Страница 327: ...1E PLC Memory In This Appendix DL105 PLC Memory...
Страница 329: ...1F European Union Directives CE In This Appendix European Union EU Directives Basic EMC Installation Guidelines...