Installation,
Wiring,
and
Specifications
2--28
Installation, Wiring, and Specifications
DL105 PLC User Manual, 3rd Edition
The F1--04SIM Input Simulator, shown to
the right, provides four switches for inputs
X0 through X3. The simulator is useful
during program development or for debug
purposes. It works by using the +24VDC
auxiliary supply output, routing the voltage
through the switches and into the inputs.
engineering
ON
OFF
FACTS
F1--04SIM
In use, the simulator can quickly provide test inputs to your ladder program. The
status of outputs is observable on the front panel LEDs, even without wiring the
outputs to any loads.
The Simulator works on all DC input versions of the DL105. DC-powered versions
need two wires from the power input to connect to the two left-most terminals on the
simulator (wiring shown below), since DC-powered units do not ge24VDC
auxiliary output. Polarity does not matter, since the inputs can be sinking or sourcing.
NOTE:
The Input Simulator will not work on DL105 micros with AC type inputs. The
+24 VDC auxiliary supply voltage is less than the required input threshold.
engineering
ON
OFF
FACTS
F1--04SIM
engineering
ON
OFF
FACTS
F1--04SIM
Slide simulator under
left-most terminals
and tighten screws.
F1--130DR/F1--130DR--CE, F1--130DD/F1--130DD--CE, F1--130DA
F1--130DR--D, F1--130DD--D only
NOTE: Never attempt to install more than one simulator on one DL105 PLC.
(see warning below)
10W
WARNING: DO NOT use the two wires as shown above on AC-powered DL105
PLCs. Doing so will permanently damage the Micro PLC and may result in
electrical shock due to the exposed circuit board of the input simulator.
F1--04SIM Input
Simulator Wiring
Содержание DL105
Страница 2: ...DL105 PLC User Manual Manual Number D1 USER M...
Страница 308: ...1B DL105 Error Codes In This Appendix Error Code Table...
Страница 314: ...1C Instruction Execution Times In This Appendix Introduction Instruction Execution Times...
Страница 324: ...1D Special Relays In This Appendix DL105 PLC Special Relays...
Страница 327: ...1E PLC Memory In This Appendix DL105 PLC Memory...
Страница 329: ...1F European Union Directives CE In This Appendix European Union EU Directives Basic EMC Installation Guidelines...