Standard
RLL
Instructions
5--26
Standard RLL Instructions
Immediate Instructions
DL105 PLC User Manual, 3rd Edition
The
Set
Immediate
instruction
immediately sets, or turns on an output or
a range of outputs in the image register
and the corresponding output point(s)
at
the time the instruction is executed
. Once
the outputs are set it is not necessary for
the input to remain on. The Reset
Immediate instruction can be used to
reset the outputs.
aaa
Y aaa
SETI
aaa
Y aaa
The
Reset
Immediate
instruction
immediately resets, or turns off an output
or a range of outputs in the image register
and the output point(s)
at the time the
instruction is executed
. Once the outputs
are reset it is not necessary for the input to
remain on.
RSTI
Operand Data Type
DL130 Range
aaa
Outputs
Y
0--177
In the following example, when X1 is on, Y2 through Y5 will be set on in the image
register and on the corresponding output points.
1
B
ENT
X1
Y2
SETI
Y5
Direct
SOFT
Handheld Programmer Keystrokes
STR
$
SET
X
SHFT
8
I
ENT
2
C
5
F
In the following example, when X1 is on, Y5 through Y22 will be reset (off) in the
image register and on the corresponding output module(s).
1
B
ENT
X1
Y2
RSTI
Y5
Direct
SOFT
Handheld Programmer Keystrokes
STR
$
SHFT
8
I
RST
S
ENT
2
C
5
F
Set Immediate
(SETI)
Reset
Immediate
(RSTI)
Содержание DL105
Страница 2: ...DL105 PLC User Manual Manual Number D1 USER M...
Страница 308: ...1B DL105 Error Codes In This Appendix Error Code Table...
Страница 314: ...1C Instruction Execution Times In This Appendix Introduction Instruction Execution Times...
Страница 324: ...1D Special Relays In This Appendix DL105 PLC Special Relays...
Страница 327: ...1E PLC Memory In This Appendix DL105 PLC Memory...
Страница 329: ...1F European Union Directives CE In This Appendix European Union EU Directives Basic EMC Installation Guidelines...