Appendix
B
DL105
Error
C
odes
B--2
DL105 Error Codes
DL105 PLC User Manual, 3rd Edition
DL105 Error Code
Description
E003
SOFTWARE
TIME-OUT
If the program scan time exceeds the time allotted to the watchdog timer, this
error will occur. SP51 will be on and the error code will be stored in V7755. To
correct this problem use AUX 55 to extend the time allotted to the watchdog
timer.
E004
INVALID
INSTRUCTION
The CPU attempted to execute an instruction code, but the RAM contents
had a parity error. Performing a program download to the CPU in an
electrically noisy environment can corrupt a program’s contents. Clear the
CPU program memory, and download the program again.
E099
PROGRAM
MEMORY
EXCEEDED
If the compiled program length exceeds the amount of available CPU RAM
this error will occur. SP52 will be on and the error code will be stored in
V7755. Reduce the size of the application program.
E151
BAD COMMAND
A parity error has occurred in the application program. SP44 will be on and
the error code will be stored in V7755 .This problem may possibly be due to
electrical noise. Clear the memory and download the program again. Correct
any grounding problems. If the error returns replace the Micro PLC.
E155
RAM FAILURE
A checksum error has occurred in the system RAM. SP44 will be on and the
error code will be stored in V7755. This problem may possibly be due to a low
battery, electrical noise or a CPU RAM failure. Clear the memory and
download the program again. Correct any grounding problems. If the error
returns replace the CPU.
E210
POWER FAULT
A short duration power drop-out occurred on the main power line supplying
power to the base.
Содержание DL105
Страница 2: ...DL105 PLC User Manual Manual Number D1 USER M...
Страница 308: ...1B DL105 Error Codes In This Appendix Error Code Table...
Страница 314: ...1C Instruction Execution Times In This Appendix Introduction Instruction Execution Times...
Страница 324: ...1D Special Relays In This Appendix DL105 PLC Special Relays...
Страница 327: ...1E PLC Memory In This Appendix DL105 PLC Memory...
Страница 329: ...1F European Union Directives CE In This Appendix European Union EU Directives Basic EMC Installation Guidelines...