There are many things to consider when designing the panel layout. The following items
correspond to the diagram shown. Note: there may be additional requirements,
depending on your application and use of other components in the cabinet.
1. Mount the bases horizontally as shown below to provide proper ventilation.
You
cannot
mount the DL105 units vertically, upside down, or on a flat
horizontal surface. If you place more than one unit in a cabinet, there must
be a minimum of 7.2” (183mm) between the units.
OK
Airflow
2. Provide a minimum clearance of 2” (50mm) between the unit and all sides of
the cabinet.
Note, remember to allow for any operator panels or other items
mounted in the door.
3. There should also be at least 3” (78mm) of clearance between the unit and
any wiring ducts that run parallel to the terminals.
Earth Ground
Panel Ground
Terminal
DL105
Power
Source
Temperature
Probe
Star Washers
Panel
Ground Braid
Copper Lugs
Panel or
Single Point
Ground
Star Washers
BUS Bar
Note: there is a minimum of 2” (30mm)
clearance between the panel door
or any devices mounted in the panel door
2”
50mm
min.
2”
50mm
min.
and the nearest DL105 component
2”
50mm
min.
Not to Scale
Micro PLC
4. The ground terminal on the DL105 base must be connected to a single
point ground. Use copper stranded wire to achieve a low impedance.
Copper eye lugs should be crimped and soldered to the ends of the
stranded wire to ensure good surface contact.
5. There must be a single point ground (i.e. copper bus bar) for all devices in
the panel requiring an earth ground return. The single point of ground must
be connected to the panel ground termination. The panel ground
termination must be connected to earth ground. Minimum wire sizes, color
coding, and general safety practices should comply with appropriate
electrical codes and standards for your area.
Panel Layout &
Clearances
Содержание DL105
Страница 2: ...DL105 PLC User Manual Manual Number D1 USER M...
Страница 308: ...1B DL105 Error Codes In This Appendix Error Code Table...
Страница 314: ...1C Instruction Execution Times In This Appendix Introduction Instruction Execution Times...
Страница 324: ...1D Special Relays In This Appendix DL105 PLC Special Relays...
Страница 327: ...1E PLC Memory In This Appendix DL105 PLC Memory...
Страница 329: ...1F European Union Directives CE In This Appendix European Union EU Directives Basic EMC Installation Guidelines...