Installation,
Wiring,
and
Specifications
2--12
Installation, Wiring, and Specifications
DL105 PLC User Manual, 3rd Edition
125 VDC Operation
Proper fusing techniques are required when operating from 125 VDC. Depending on
your ground reference, the hot lead must be fused. A DC failure can maintain an arc
for much longer time and distance. Typically, the main bus is fused at a higher level
than the branch device, which in this case would be the DL105 unit. This double
fusing technique is required when operating from direct current. The recommended
fuse size for the branch circuit to the DL105 is 0.5A (for example, a Littlefuse 312.500
or equivalent).
12/24 VDC Operation
When operating at these lower dc voltages, wire gauge size is just as important as
proper fusing techniques. Using large conductors minimizes the voltage drop in the
conductor. Each DL105 input power terminal can accommodate one 14 AWG or two
16 AWG wires. Each terminal block junction and/or connection creates a voltage
drop, so try to keep the number of connections to a minimum. In general, when using
12/24 VDC input power, observe the same double fusing techniques that are used
with 125 VDC input power. The recommended fuse size for the branch circuit to the
DL105 is 1A (for example, a Littlefuse 312.001 or equivalent).
The power source must be capable of suppling voltage and current complying with
individual Micro PLC specifications, according to the following specifications:
Part Numbers
F1--130AR, F1--130DR,
F1--130AD, F1--130DD,
F1--130AA, F1--130DA
F1--130DR--D,
F1--130DD--D
Input Voltage Range
85--132 VAC (110 nominal)
170--264 VAC (220 nominal),
100 -- 264 VDC (125 nominal)
10 -- 30 VDC (12 to 24VDC)
with less than 10% ripple
Maximum Inrush Current
12 A, <1/2 mS
12 A, <1/2 mS
Maximum Power
30 VA (for AC power)
30 W (for DC power)
10W (0.3A @ 30VDC)
Voltage Withstand (dielectric)
1 minute @ 1500 VAC between primary, secondary, field
ground
Insulation Resistance
> 10 M
Ω
at 500 VDC
Auxiliary 24 VDC Output
21.6--26.4 VDC
Ripple less than 200 mV p-p
500 mA max, isolated.
None
NOTE:
The rating between all internal circuits is BASIC INSULATION ONLY.
External
Power Source
Содержание DL105
Страница 2: ...DL105 PLC User Manual Manual Number D1 USER M...
Страница 308: ...1B DL105 Error Codes In This Appendix Error Code Table...
Страница 314: ...1C Instruction Execution Times In This Appendix Introduction Instruction Execution Times...
Страница 324: ...1D Special Relays In This Appendix DL105 PLC Special Relays...
Страница 327: ...1E PLC Memory In This Appendix DL105 PLC Memory...
Страница 329: ...1F European Union Directives CE In This Appendix European Union EU Directives Basic EMC Installation Guidelines...