The following table lists program syntax and runtime error codes. Error detection
occurs during a Program-to-Run mode transition, or when you use AUX 21 -- Check
Program. The CPU will also turn on SP52 and store the error code in V7755.
Appendix B provides a more complete description of the error codes.
Error Code
Description
E4**
No Program in CPU
E401
Missing END statement
E402
Missing LBL
E406
Missing IRT
E421
Duplicate stage reference
E422
Duplicate SBR/LBL reference
E431
Invalid ISG/SG address
E436
Invalid INT address
E438
Invalid IRT address
E440
Invalid Data Address
E441
ACON/NCON
E451
Bad MLS/MLR
Error Code
Description
E452
X input used as output coil
E453
Missing T/C
E454
Bad TMRA
E455
Bad CNT
E456
Bad SR
E461
Stack Overflow
E462
Stack Underflow
E463
Logic Error
E464
Missing Circuit
E471
Duplicate coil reference
E472
Duplicate TMR reference
E473
Duplicate CNT reference
Program Error
Codes
Содержание DL105
Страница 2: ...DL105 PLC User Manual Manual Number D1 USER M...
Страница 308: ...1B DL105 Error Codes In This Appendix Error Code Table...
Страница 314: ...1C Instruction Execution Times In This Appendix Introduction Instruction Execution Times...
Страница 324: ...1D Special Relays In This Appendix DL105 PLC Special Relays...
Страница 327: ...1E PLC Memory In This Appendix DL105 PLC Memory...
Страница 329: ...1F European Union Directives CE In This Appendix European Union EU Directives Basic EMC Installation Guidelines...