Standard
RLL
Instructions
5--15
Standard RLL Instructions
Boolean Instructions
DL105 PLC User Manual, 3rd Edition
The Positive Differential instruction is
typically known as a one shot. When the
input logic produces an off to on
transition, the output will energize for one
CPU scan.
A aaa
PD
Operand Data Type
DL130 Range
A
aaa
Inputs
X
0--11
Outputs
Y
0--7
Control Relays
C
0--377
In the following example, every time X1 makes an off to on transition, C0 will
energize for one scan.
STR
$
1
B
ENT
SHFT
CV
P
3
D
SHFT
0
A
ENT
C0
PD
X1
Handheld Programmer Keystrokes
Direct
SOFT
The Set instruction sets or turns on an
image register point/memory location or
a consecutive range of image register
points/memory locations. Once the
point/location is set it will remain on until it
is reset using the Reset instruction. It is
not necessary for the input controlling the
Set instruction to remain on.
A aaa
SET
aaa
Optional
memory range
The Reset instruction resets or turns off
an image register point/memory location
or
a
range
of
image
registers
points/memory locations. Once the
point/location is reset it is not necessary
for the input to remain on.
A aaa
RST
aaa
Optional
memory range
Operand Data Type
DL105 Range
A
aaa
Inputs
X
0--11
Outputs
Y
0--7
Control Relays
C
0--377
Stage
S
0--377
Timer
T
0--77
Counter
CT
0--77
DS
Used
HPP Used
Positive
Differential
(PD)
DS
Used
HPP Used
Set
(SET)
DS
Used
HPP Used
Reset
(RST)
Содержание DL105
Страница 2: ...DL105 PLC User Manual Manual Number D1 USER M...
Страница 308: ...1B DL105 Error Codes In This Appendix Error Code Table...
Страница 314: ...1C Instruction Execution Times In This Appendix Introduction Instruction Execution Times...
Страница 324: ...1D Special Relays In This Appendix DL105 PLC Special Relays...
Страница 327: ...1E PLC Memory In This Appendix DL105 PLC Memory...
Страница 329: ...1F European Union Directives CE In This Appendix European Union EU Directives Basic EMC Installation Guidelines...